Notification Appliance Wiring; Class A Supervised Wiring; Class A Output Notification Circuits; Class A Supervised Input Circuits - Honeywell Gamewell FCI GFPS-9 Installation Manual

Supplementary notification appliance circuit module
Table of Contents

Advertisement

9001-0024
A typical application of the trouble relay is to connect the GFPS-9 normally closed (N.C.) contacts in series with
the EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control panel when
the GFPS-9 opens its trouble contacts.
Note:
The N.C. contact is the contact that is closed when the GFPS-9 has power and there are no trouble conditions.
4.5

Notification Appliance Wiring

Note:
Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device you have chosen will work
with this feature.
For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2
must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles,
input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be
inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1
remains active. If input 1 is not active, then input 2 is ignored.
4.5.1

Class A Supervised Wiring

Figure 4-4 shows how to wire for Class A input and output supervision. Use in/out wiring methods for proper
supervision. (Refer to Appendix A for notification appliances compatible with the GFPS-9.)

Class A Output Notification Circuits

The configuration shown in Figure 4-4 shows two, 3 A devices wired as Class A. When using the outputs as
Class A circuits, loop the wiring back to the corresponding circuit pair. For Class A wiring, no external EOL is
necessary since it is built into the GFPS-9 board.

Class A Supervised Input Circuits

The configuration shown in Figure 4-4 shows Class A supervised wiring from a fire alarm control panel to the
GFPS-9 board. Pay close attention to the polarities when wiring a panel to the GFPS-9 and follow these
requirements:
When wiring to Terminal 18 on the GFPS-9, you must use two separate wires. Do not loop a single wire or
Must be connected to
a power limited source
Figure 4-3 Trouble Relay Connection Example
Important!
4-10

Advertisement

Table of Contents
loading

Table of Contents