2: Main Control Unit; Installation Standards And Codes - Honeywell Notifier ACPS-610/E Manual

Addressable charger/power supply
Table of Contents

Advertisement

Introduction
Utilizes wire sizes 10-14 AWG. (5.26 mm.
Charging current: 2.0 A, 5.0 A, or OFF (Software selectable)
Based on battery size programming.
Charging voltage: 27.6 VDC (nominal)
To calculate expected standby operating times, see Section 5.2 on page 49.
Battery Fuse - (F2)
15A, Slo-Blow Fuse P/N 12057
1.2.2 Main Control Unit
Output Circuits - TB3, TB4, TB5, TB6
NAC Output
•Nominal voltage: 24 VDC, regulated
•1.5 A maximum for any output circuit configured as a NAC.
•At alarm current level with 12-18 AWG, no more than a 1.2 V drop at the end of the circuit,
or sized to provide the minimum rated operation voltage of the appliances used.
Output Power Circuit, resettable, door holder, and general power.
•Nominal voltage: 24 VDC, special applications.
•1.5 A max. with charger enabled.
•2.5 A max with charger disabled.
•Maximum ripple voltage: 200 mV p-p.
•12-18 AWG, no more than a 1.2 V drop at the end of the circuit, or sized to provide the
minimum rated operation voltage of the appliances used.
Zero (0) ohms from any output to earth ground will cause ground fault detection.
Refer to the Device Compatibility Document for compatible devices, 24 VDC detectors, and
notification appliances.
SLC Circuit - TB2
Average SLC current is 1.0 mA. The maximum resistance of the SLC wiring from any device
to the FACP should not exceed 50 ohms.
Utilizes wire sizes 12-18 AWG (3.31 mm.
UZC - TB1
24 VDC coded input (UZC or Sync Signal)
Utilizes wire sizes 12 – 22 AWG (3.31 mm.2 – 0.326 mm.
Full Speed USB 2.0 - J3
USB Type B connector

1.3 Installation Standards and Codes

The ACPS-610/E complies with the following standards:
NFPA 72 National Fire Alarm Code
Underwriters Laboratories:
UL 864 Standard for Control Units and Accessories for Fire Alarm Systems
Underwriters Laboratories of Canada (ULC):
ULC-S527-M99: Standard of Control Units for Fire Alarm Systems
ULC-S524: Standard for the Installation of Fire Alarm Systems
8
Installation Standards and Codes
2
2
– 2.08 mm.
)
2
2
– 0.821 mm.
)
2
) twisted pair wire
ACPS-610/E Manual — P/N 53018:A1 07/31/2007