Supplying Voltage
Ac mains frequency
Current consumption by mains
Output Voltage
Minimum output Voltage
Switching-off threshold Voltage
Output current
Max current for battery recharge
Max current for charges (I
)
max.a
Max current for charges without battery recharging (I
Max current for any output
Minimum current for charges (I
Regulations towards mains variations at full charge (+10% / -15%)
Regulations towards charge variations (0 to 100%)
Ripple at full charge
Compensation of output Voltage according to temperature
Protection against battery polarity inversion
Recommended batteries: 2 x 12 V in series, 17 Ah housing with inflammability
class UL-94-V2 or better
Max current without mains supply
Alarm threshold of battery internal resistance
Missing mains and failure output relay – dry contacts
Tab 1
Size in mm.
Weight
Operating temperature
Humidity
cooling
Installation site
Tab 2
FUSE1
Fuse of the 230 Vac supplying input (T4 AL 250V). Not replaceable
F1
Battery fuse (T6,3 AL 250 V)
F2
Electronic Fuse related to output A
Tab 3
The power supply has been certified using YUASA NP 17-12 batteries
SECURITY INSTRUCTIONS
1.
For mains input and DC outputs + alarms, use separate holes on the bottom of the box to pass the cables. Furthermore, the
material of the joint pipe/box must have a flammability class V-1 or better
2.
The relay contact "GUASTO" and "RETE" must be connected only to circuits operating with SELV Voltage.
3.
For AC supplying, provide a 6A protection bi-pole magneto-dynamic switch, easy to access
4.
The wires must have a section of 1,5mm and be equipped with adequate buttonholes where they are subject to pressure
contact.
5.
The installation of the power supply must be carried out by qualified personnel aware of the security norms EN60950 and
concerning power supplies CEI-64-8.

INSTALLATION

Mechanical mounting
This device has to be mounted on vertical stable walls, suitable to support the power supply, by means of 4 screws with 6mm diameter,
for spacers and screws on the 4 holes on the bottom of the box. The battery must be fixed using the strap given within.
S-326.1-ALI50EN-ENG A. 1 05-2015
ELECTRICAL SPECIFICATIONS
)
max.b
)
min
MECHANICALSPECIFICATIONS
ENVIRONMENTAL SPECIFICATIONS
230 Vac +10% / -15%
50 Hz sinusoidal
1,1 A max. ( full load )
27,6 Vdc ( -15% / +10%)
20 Vdc at max charge, with mains absence and battery
discharged
20 Vdc
5 A max. (see Fig.4)
1 A
4 A
4,5 A
1,5 A
0 A
Better than 1%
Better than 1%
1 Vpp ( at 195,5 Vac ) 30mVpp ( at 253 Vac )
4 mV/ K
Diode
Type:YUASA NP 17-12 or equivalent.
4 A
1Ω
25 Vac or 60 Vdc 1A MAX
width 430; height 375; depth 120
6,25 Kg
from -5°C to +40°C
from 5% to 93% ± 2 %
air cooling
sheltered from atmospheric agents
FUSES
F4
Electronic Fuse related to output B
F3
Electronic Fuse related to output C