Equalize Duration: Set the duration time (10-240 minutes) for the equalize
charge voltage to be applied (as recommended by your battery
manufacturer).
Equalize Interval: Set the equalize charge interval (0 – 180 days) so the
system will perform an automatic equalize charge once every interval time
has elapsed. Set this time to 0 (default) to disable the automatic equalize
charge.
Day of Week: Select the day of the week that the automatically recurring
equalize charge should take place, or select "Any" to allow an Equalize
charge to take place on any day of the week.
Day of Week takes precedence over Equalize Interval.
[note]
Start Time: Set the time of day for automatically recurring equalize charges
to start. The time must be entered using 24-hour time format.
NTP Time Synchronization must be enabled on the Communications Basic
Setup page to enable automatically recurring equalize charges.
[Note] that an equalize charge can only be initiated when the battery is fully
charged. If the system is unable to start an equalize charge at the selected
Start Time, it will attempt again at the same time next day, or next week if a
specific Day of Week is selected.
Click the Manual Equalize Charge button to manually initiate an equalize
charge for the set duration once the battery is fully charged.
[note] System will state that Manual Equalize Charge is Not Ready, if
battery is not yet fully charged
The date of the last equalize charge and the duration of that charge is noted
here, along with the scheduled date and time of the next automatic
equalize charge, if an Equalize Interval or Day of Week has been set. This
information is to help track where the system is within the automatic
charge cycle.
Battery Low SOC Alarm
This setting is only available if the system is configured for use with a lead-acid
type battery.