Riello RS 45/E BLU Installation, Use And Maintenance Instructions page 35

Forced draught gas burners
Table of Contents

Advertisement

Parameter
No.
Description
par.
Gas: selection of flame sensor
221
0 = QRB.../ QRC
1 = ION / QRA
222
Gas: Selection of the pre-purging function
0 = deactivated
1 = activated
223
Maximum repeats of minimum gas pressure switch intervention
225
Gas: pre-purging time
226
Gas: pre-ignition time
230
Gas: interval 1
232
Gas: interval 2
233
Gas: post-combustion time
234
Gas: post-purging time
242
Gas: emptying time (valve leak detection)
243
Gas: atmospheric test time (valve leak detection)
244
Gas: filling time (valve leak detection)
245
Gas: pressure test time (valve leak detection)
261
Oil: selection of flame sensor
0 = QRB.../ QRC...
1 = ION / QRA
265
Oil: pre-purging time
266
Oil: pre-ignition time
270
Oil: interval 1
272
Oil: interval 2
273
Oil: post-combustion time
274
Oil: post-purging time
281
Oil: selection transformer ignition phase TA
0 = brief pre-ignition (Ph38)
1 = long pre-ignition (with fan) (Ph22)
400
Air/fuel modulation curve
401
Checking fuel servomotor
402
Checking air servomotor
500
Positioning of servomotors
501
Position of the fuel servomotor in absence of flame
Index 0 = standby position
Index 1 = pre-purging position
Index 2 = post-purging position
Unit of
Number of
Modifica-
measure-
elements
tion
ment
1
-
Modification
1
-
Modification
1
-
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
-
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
-
Modification
13
(°)
Modification
13
(°)
Modification
3
(°)
Modification
Values interval
Degree of pre-
Min.
Max.
cision
0
1
1
0
1
1
1
16
1
20 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
108 min
0.2 s
0.2 s
3s
0.2 s
0.2 s
60s
0.2 s
0.2 s
3s
0.2 s
0.2 s
60s
0.2 s
0
1
1
15 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 s
0.2 s
0.2 s
108 min
0.2 s
0
1
1
90°
0.1°
90°
0.1°
90°
0.1°
Predefined
Access mode
setting
1
Parameters mode
1
Parameters mode
16
Parameters mode
20 s
Parameters mode
2 s
Parameters mode
2 s
Parameters mode
2 s
Parameters mode
8 s
Parameters mode
0.2 s
Parameters mode
3 s
Parameters mode
10 s
Parameters mode
3 s
Parameters mode
10 s
Parameters mode
0
Parameters mode
15 s
Parameters mode
2 s
Parameters mode
2 s
Parameters mode
2 s
Parameters mode
8 s
Parameters mode
0.2 s
Parameters mode
0
Parameters mode
0°; 0°; 15°; not
Parameters mode
defined
0°; 90°; 45°; not
Parameters mode
defined
0°; 0°; 15°
Parameters mode