• To use the inverter of FR-F820-00930(22K) or lower and FR-F840-00620(30K) or lower (IP20) outside of an enclosure in the environment of pollution
degree 2, fix the fan cover with fan cover fixing screws enclosed.
• On the input and output of the inverter, use cables of the type and size set forth in EN 60204-1 or IEC 60364-5-52.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30 VDC, 0.3 A. (Relay output has basic isolation from the
inverter internal circuit.)
• Control circuit terminals on
• Environment (For the detail, refer to the Instruction Manual (Detailed).)
LD rating: -10 to +50°C (14 to 122°F)
Surrounding air temperature
SLD rating: -10 to +40°C (14 to 104°F)
Ambient humidity
95% RH or less
Maximum altitude
2500 m

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
 Branch circuit protection
Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
For the FR-F820 series, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided. (Use a product which
conforms to the EN or IEC Standard.)
FR-F820-[]
Rated fuse voltage (V)
Without power factor
improving reactor
Fuse allowable
rating (A)
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F820-[]
Rated fuse voltage (V)
Without power factor
improving reactor
Fuse allowable
rating (A)
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power factor
improving reactor
Fuse allowable
rating (A)
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power factor
improving reactor
Fuse allowable
rating (A)
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)


Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Short circuit ratings
• 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 240 V Maximum.
• 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 500 V Maximum.
14
Appendix
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00105(2.2K) to 00250(5.5K)
FR-F840-00083(3.7K), 00126(5.5K)
page 4
are safely isolated from the main circuit.
During Operation

00046
00077
00105
00167
(0.75K)
(1.5K)
(2.2K)
(3.7K)
240 V or more
15
20
30
40
15
20
20
30
15
15
25
40
00930
01250
01540
01870
(22K)
(30K)
(37K)
(45K)
240 V or more
225
300
350
400
200
250
300
350
225
300
350
450
00023
00038
00052
00083
(0.75K)
(1.5K)
(2.2K)
(3.7K)
500 V or more
6
10
15
20
6
10
10
15
15
15
15
20
00930
01160
01800
02160
(45K)
(55K)
(75K)
(90K)
500 V or more
200
250
175
200
250
300
225
250
450
450
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00340(7.5K) to 00930(22K)
FR-F840-00170(7.5K) to 00620(30K)
In Storage
-20 to +65°C (-4 to +149°F)
95% RH or less
2500 m
00250
00340
00490
00630
(5.5K)
(7.5K)
(11K)
(15K)
60
80
150
175
50
70
125
150
60
80
110
150
02330
03160
03800
04750
(55K)
(75K)
(90K)
(110K)
500
400
500
600
700
500
700
900
1000
00126
00170
00250
00310
(5.5K)
(7.5K)
(11K)
(15K)
30
40
70
80
25
35
60
70
30
40
60
70
02600
03250
03610
04320
(110K)
(132K)
(160K)
(185K)
350
400
500
600
500
During Transportation
-20 to +65°C (-4 to +149°F)
95% RH or less
10000 m
00770
(18.5K)
200
200
190
00380
00470
00620
00770
(18.5K)
(22K)
(30K)
(37K)
90
110
150
175
90
100
125
150
90
100
150
175
04810
05470
06100
06830
(220K)
(250K)
(280K)
(315K)
700
800
900
1000