Installation Mechanical
temperature is 65°F. Condenser piping must be in accordance
with all local and national codes. Condenser piping
components generally function identically to those in the
evaporator piping system. In addition, cooling tower systems
may include a manual or automatic bypass valve that can alter
water flow rate to maintain condensing pressure. Well (city)
water condensing systems should include a pressure reducing
valve and water regulating valve. A pressure reducing valve
should be installed to reduce water pressure entering the
condenser. This is required only if water pressure exceeds
nameplate maximums. This is also necessary to prevent
damage to the disc and seat of the water regulating valve that
can be caused by excessive pressure drop through the valve.
CG-SVX044F-EN
29