Troubleshooting

10.1

Operational problems

Operational problems can be solved by troubleshooting the following areas:
▪ Alarms
▪ Leakage (fluid side)
▪ Abnormal noise in the heat pump or radiator system
▪ Hot water
▪ Heating
▪ Other issues
There may be more than one way of troubleshooting a cause.
10.1.1
Alarms
Error code
Description
00
Communication failure
01
Return water sensor (T9) failure
02
Supply water sensor (T8) failure
03
Water flow switch protection
04
Phase sequence error (only applies to 3-phase models)
05
Excessive temperature difference between supply and return water (>13°C)
06
Internal electrical heater overheat protection (>85°C)
07
Condenser overheat protection
08
Hot water tank sensor (T3) failure
09
Buffer tank sensor (T2) failure
10
High pressure protection
11
Low pressure protection
12
Supply water temperature too high
13
Supply water temperature too low (cooling mode only)
14
Return gas temperature sensor (T5) failure
15
Exhaust gas temperature sensor (T4) failure
16
Exhaust gas temperature overheat protection
17
Null
18
Frost protection, step 2 (non-fault)
19
Frost protection, step 1 (non-fault)
20
Air temperature sensor (T1) failure
21
Heating coil sensor (T7) failure
22
Cooling coil sensor (T6) failure
23
Exceeded operation range warning (non-fault)
32
DHP-AT