Quantum Scalar i500 Upgrade Instructions

Tape library firmware upgrade
Hide thumbs Also See for Scalar i500:

Advertisement

Scalar i500 Library Firmware
This document describes how to download Scalar i500 library firmware from
upgrade library firmware using the web client.
If you are currently running library firmware version 320G.GS004 or
CAUTION
400G.GS006, you must first install and run the Library Service Utility
before upgrading firmware. If you do not first run the Library Service
Utility, then the firmware upgrade may not complete successfully. The
Library Service Utility and installation instructions are located in the ".zip"
file that contains the firmware download files.
If you are currently running library firmware prior to version 320G.GS004,
do not upgrade to version 320G.GS004 or 400G.GS006, but instead
upgrade to the latest version. You will not need to run the Library Service
Utility.
Be aware that if you downgrade from one major firmware version to an earlier
Note
major version, library configuration settings will be reset to the factory defaults.
You can restore the other configurable items using a configuration file that was
saved when the earlier version of library firmware was installed on the library, or
you can reconfigure your library's settings. For more information, see the Scalar
i500 User's Guide.
Downgrading Library Firmware—If a library is running firmware version 400G or
Note
higher, the following restrictions on downgrading apply:
• If your library is Quantum branded, you can downgrade to firmware version 400G
or higher. (There is no lower version of Quantum-branded firmware.)
• If your library is ADIC branded and has Fibre-Channel I/O blades installed, you
can downgrade to firmware version 400G or higher. You cannot downgrade to a
lower version than 400G.

Downloading Library Firmware

Required item: Computer with Internet access
1
Using a web browser on a computer, do the following:
a. Go to www.quantum.com.
b. Click the I want to... drop-down list and select Download Software.
2
Select the i500 library from the product list. Select Tape Libraries > Scalar > Scalar i500.
Copyright 2008 by Quantum Corporation. All rights reserved. Your right to copy this document
is limited by copyright law. Making copies or adaptations without prior written authentication
of Quantum Corporation is prohibited by law and constitutes a punishable violation of the law.
Upgrade Instructions
www.quantum.com
and
6-01739-05 Rev A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Scalar i500 and is the answer not in the manual?

Questions and answers

Summary of Contents for Quantum Scalar i500

  • Page 1 Click the I want to... drop-down list and select Download Software. Select the i500 library from the product list. Select Tape Libraries > Scalar > Scalar i500. Copyright 2008 by Quantum Corporation. All rights reserved. Your right to copy this document is limited by copyright law.
  • Page 2 On the Scalar i500 page that opens, click on the Firmware link. Both the library firmware and drive firmware are contained in the same download file. Locate the firmware you need depending on the type of tape drives in your library and click on the Download Now button.
  • Page 3 If the reboot process fails, the library will retry every 10 minutes until the library successfully restarts. b. From the Reports menu, select About > Scalar i500. The About Scalar i500 screen appears.

Table of Contents