Section 11 − Auxiliary Power Guidelines - Miller Big Blue 302D Owner's Manual

Table of Contents

Advertisement

SECTION 11 − AUXILIARY POWER GUIDELINES
11-1. Selecting Equipment
11-2. Grounding Generator To Truck Or Trailer Frame
2
1
2
3
OR
1
GND/PE
OR
Electrically bond generator
frame to vehicle frame by
metal-to-metal contact.
Be sure equipment
has this symbol
and/or wording.
3
4
2
1
Auxiliary Power Receptacles
− Neutral Bonded To Frame
2
3-Prong Plug From Case
Grounded Equipment
3
2-Prong Plug From Double
Insulated Equipment
aux_pwr 2/99 − Ref. ST-159 730 / ST-800 577
1
Generator Base
2
Metal Vehicle Frame
3
Equipment Grounding
Terminal
4
Grounding Cable
Use #10 AWG or larger insulated
copper wire.
Y If unit does not have GFCI re-
ceptacles, use GFCI-pro-
tected extension cord.
S-0854
OM-497 Page 51