Technical Data; Overall Dimensions - Riello 484 M1 Installation, Use And Maintenance Instructions

Gas oil / kerosene burners
Table of Contents

Advertisement

4.3

Technical data

Thermal power - Output
Operation
Fuel
Gas oil
net calorific value
density
viscosity at 20 °C
Kerosene
net calorific value
density
viscosity at 20 °C
Electrical supply
Motor
Ignition transformer
Absorbed electrical power
Electrical protection
Reference conditions: ambient temperature 20°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
4.4

Overall dimensions

The maximum dimensions of the burner are given in Fig. 1.
(*) It is possible with a spacer upon request
Technical description of the burner
1190 ÷ 5340 kW - 100 ÷ 450 kg/h
2-stage progressive/Modulating (with kit)
Gas oil and Blends of gas oil and bio fuel (FAME in accordance with EN
14214) up to 10%
kWh/kg
Mcal/kg
kg/dm
3
2
mm
/s max
kWh/kg
Mcal/kg
kg/dm
3
2
mm
/s max
3N ~ 50 Hz 400 / 230 V
3 ~ 50 Hz 230 V
50.2A / 230V - 29A / 400V
Primary: 2A - Secondary: 2 x 6,5 kV - 35 mA
18 kW
IP 40 according EN 60529 (IEC 529-1989)
GB
9
11.86
10.2 (10.200 kcal/kg)
0.82 - 0.85
6 (1.5 °E - 6 cSt)
11.97
10.3 (10.300 kcal/kg)
0.77 - 0.83
6 (1.5 °E - 6 cSt)
Tab. A
D2904
Fig. 1
20036074