Installation, use and maintenance instructions
Kerosene burners
One stage operation
CODE
3748959
3748941
MODEL
RDB3 150/200
RDB3.2 33/44
TYPE
489 T50
490 T59
2902852 (9) - 06/2022

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RDB3.2 33/44 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Riello RDB3.2 33/44

  • Page 1 Installation, use and maintenance instructions Kerosene burners One stage operation CODE MODEL TYPE 3748959 RDB3 150/200 489 T50 3748941 RDB3.2 33/44 490 T59 2902852 (9) - 06/2022...
  • Page 2 Original instructions...
  • Page 3: Table Of Contents

    Contents Declaration....................................3 Information and general warnings............................4 Information about the instruction manual........................4 2.1.1 Introduction ..................................4 2.1.2 General dangers ................................4 2.1.3 Danger: live components ..............................4 Guarantee and responsibility ............................5 Guidance for the use of bio fuel blends up to 10% where gas oil use is permitted by the appliance Manufacturer ..5 2.3.1 Information and general instructions..........................
  • Page 4 Contents Maintenance ....................................22 Notes on safety for the maintenance..........................22 Maintenance programme ..............................22 9.2.1 Maintenance frequency ..............................22 9.2.2 Checking and cleaning ..............................22 9.2.3 Safety components................................23 10 Faults / Solutions ..................................24 2902852...
  • Page 5: Declaration

    Declaration Declaration Declaration of Conformity in accordance with ISO / IEC 17050-1 These products are in compliance with the following Technical Standards: • EN 12100 • EN 267 According to the European Directives: 2006/42/EC Machine Directive 2014/35/EU Low Voltage Directive EMC 2014/30/EU Electromagnetic Compatibility The quality is guaranteed by a quality and management system certified in accordance with ISO 9001:2015.
  • Page 6: Information And General Warnings

    Information and general warnings Information and general warnings Information about the instruction manual 2.1.1 Introduction 2.1.3 Danger: live components The instruction manual supplied with the burner: This symbol indicates operations which, if not car-  is an integral and essential part of the product and must not ried out correctly, lead to electric shocks with le- be separated from it;...
  • Page 7: Guarantee And Responsibility

    All components within the hydraulic circuit suitable for manual, operating negligence, incorrect installa- bio fuel use and supplied by Riello will be identified as Bio com- tion and carrying out of non authorised modifica- patible. No warranty is given in relation to the use of components...
  • Page 8: Information And General Instructions

    If this is not completed then due to the hydro- In no event shall Riello (and its subsidiaries) be liable for any in- scopic nature of Bio fuel, it will effectively clean the tank,...
  • Page 9: Safety And Prevention

    Safety and prevention Safety and prevention Introduction The burners have been designed and built in compliance with the type and pressure of the fuel, the voltage and frequency of the current regulations and directives, applying the known technical electrical power supply, the minimum and maximum deliveries for rules of safety and envisaging all the potential danger situations.
  • Page 10: Technical Description Of The Burner

    In case of use with gas oil containing up to 10% Hexagonal key ..............No. 1 Bio blend, it will be essential to use flexible oil Screws and terminal screw for feeding cable...... No. 3 lines suitable for bio fuel use. Please contact Riello for further information. 2902852...
  • Page 11: Burner Dimensions

    Technical description of the burner Burner dimensions Flange Burner D1844 Fig. 2 Firing rates The MAXIMUM OUTPUT is chosen from within the diagram area The work point may be found by plotting a vertical line from the (Fig. 3). desired delivery and a horizontal line from the pressure in the combustion chamber.
  • Page 12: Installation

    Installation Installation Notes on safety for the installation After carefully cleaning all around the area where the burner will The installation of the burner must be carried out be installed, and arranging the correct lighting of the environ- by qualified personnel, as indicated in this manual ment, proceed with the installation operations.
  • Page 13: Installer/Servicer Notes For The Use Of Gas Oil With Bio Blends Up To 10% Where Gas Oil Use Is Permitted By The Appliance Manufacturer

     The burner hydraulic components and flexible oil lines must burner technical manual). be suitable for bio fuel use (check with Riello if in doubt).  If a Bio blend is in use the installer must seek information Riello have carefully chosen the specification of the bio com-...
  • Page 14: Boiler Fixing

    Installation Boiler fixing  Put on the flange 1)(Fig. 6) the screw and two nuts.  Widen, if necessary, the insulating gasket holes (5), (see Fig. 7).  Fix the flange 1)(Fig. 8) to the boiler door 4) using screws 2) and (if necessary) the nuts 3) interposing the insulating gas- ket 5).
  • Page 15: Burner Assembly

    Installation Burner assembly CF Application BF Application In case of CF applications, the burner shall not operate without protection (A) of the suction inlet. The temperature of the incoming air must not exceed 70 °C. CAUTION For correct BF application, the burner must be in- E1556 stalled on an appropriate BF boiler.
  • Page 16: Hydraulic Systems

    In case of use with gas oil containing up to 10% Bio blend, it will be essential to use flexible oil lines suitable for bio fuel use. WARNING Please contact Riello for further information. D10934 Fig. 11 Key (Fig. 11)
  • Page 17: One Pipe System

    Usually the tank is lower than the burner. You are advised to use additional filters on the fuel supply line. Riello recommends a good quality fuel filter at the CAUTION tank (Fig. 12 - Fig. 13) and a secondary filter (60 ...
  • Page 18: Two Pipe System

    You are advised to use additional filters on the fuel supply line. Riello recommends a good quality fuel filter at the CAUTION tank (Fig. 14) and a secondary filter (60  for gas oil and 15  for kerosene) are used to protect the burner pump and nozzle from contamination.
  • Page 19: Electrical System

    Electrical system Electrical system Notes on safety for the electrical wiring  The electrical wiring must be carried out with the electrical supply disconnected.  Electrical wiring must be carried out by qualified personnel and in compliance with the regulations currently in force in the country of destination.
  • Page 20: Electrical Wiring

    Electrical system Electrical wiring 7.2.1 Control box 50Hz - 230V This operation must be performed with the burner turned off and mains power disconnected. DANGER Main switch To remove the control box (Fig. 16) from the burner follow of the instruction: ...
  • Page 21: Start-Up, Calibration And Operation Of The Burner

    Start-up, calibration and operation of the burner Start-up, calibration and operation of the burner Notes on safety for the first start-up The first start-up of the burner must be carried out Check the correct working of the adjustment, com- by qualified personnel, as indicated in this manual mand and safety devices.
  • Page 22: Nozzles Installation

    Start-up, calibration and operation of the burner Nozzles installation The burner complies with the emission requirements of the The use of nozzles other than those specified by EN 267 standard. manufacturer inadequate regular In order to guarantee that emissions do not vary, recommended maintenance may result into emission limits non- and/or alternative nozzles specified by the manufacturer in the In- conforming to the values set forth by the...
  • Page 23: Air Damper Adjustment

    Start-up, calibration and operation of the burner Air damper adjustment The settings indicated in the schedule refer to the combustion- Each installation however, has its own unpredictable working chamber with “zero” depression. This regulation is purely indica- conditions: actual nozzle output; positive or negative pressure in tive.
  • Page 24: Maintenance

    Burner lines suitable for bio fuel use. Check for excess wear or loose screws and clean the outside of Please contact Riello for further information. the burner. Any contact with elements such solvents, thinners Check to make sure that no dust has accumulated inside the fan...
  • Page 25: Safety Components

    Maintenance Then carry out a combustion check verifying: 9.2.3 Safety components – Smoke temperature at the chimney; The safety components must be replaced at the end of their life – Content of CO (%); cycle indicated in Tab. F. The specified life cycles do not refer to –...
  • Page 26: Faults / Solutions

    Faults / Solutions Faults / Solutions Here below you can find some causes and the possible solutions When lock out lamp lights the burner will attempt to light only after for some problems that could cause a failure to start or incorrect pushing the reset button.
  • Page 28 RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.riello.it http:// www.riello.com Subject to modifications...