Riello 484 M1 Installation, Use And Maintenance Instructions page 18

Gas oil / kerosene burners
Table of Contents

Advertisement

Pressure controller
D2001
1 - Pressure switch plug
2 - Manometer for pressure in delivery line
3 - Manometer for pressure in return line
4 - Eccentric adjusting screw
5 - Ring for piston stop
6 - Nut and lock-nut for piston rating
7 - Eccentric locking screws
8 - Variable eccentric
9 - Cover
The eccentric (8) setting should be carried out as follows:
remove the cover (9), loosen the screws (7), and act on the screw
(4) to obtain the desired eccentricity. Turn clockwise (+) the
screw (4) to increase the eccentricity, increasing the difference
between the min. and max. capacity of the nozzle; turn anticlock-
wise (-) to decrease the eccentricity and, consequently the differ-
ence between the min. and max. capacity of the nozzle.
The proper setting of the eccentric (8) is possible when its op-
eration
field
follows the
(20°÷130°): so, that any variation of the servomotor position
corresponds to a pressure variation.
Never let the piston batter: the stop ring (5) determines the
max. stroke.
When the setting is carried out, verify manually that no slow-
down occurs between 20° and 130° and further the maximum
and minimum pressures correspond to those chosen as per
diagram of page 15.
If you wish to check the delivery capacity of the nozzle, pro-
ceed as follows:
Open the burner according to instructions at page 13, place
the nozzle, simulate the start-up and then proceed with the
weighing at the maximum and minimum pressures.
If at maximum capacity of the nozzle (maximum pressure in
the return line) pressure fluctuations are detected on the ma-
nometer (3), slightly decrease the pressure till their complete
elimination.