This applies in particular to oil-related parts such as the pump, solenoid valve, oil ilter and hoses. It is very important when carrying out a service to replace old parts with new parts of the same quality. Bentone B45-2 RME...
Page 5
• Install a tube in the chimney • Install a draught regulator (dilutes the lue gases during operation and dries them up during standstill) • Increase the oil quantity • Raise the lue gas temperature by removing turbulators, if any, in the boiler. Bentone B45-2 RME...
Setting of ignition electrodes and brake plate *NB It is important that the spark does not strike against the brake plate or nozzle 5,0-6,0 3,5-4,0 7,0-9,0 2,0-3,0 Insertion length, Burner tube, burner tube Dimension B 2.2.1 Burner output 45,5 kg/h Bentone B45-2 RME...
It should be noted that the scattering angle and distribution pattern changes with pump pressure. Nozzle: 45° Solid/semi-solid 60° Solid/semi-solid The burner pump is factory set at 14 bar and 80° Solid/semi-solid test operated using Roadway 80. Pump pressure 14 bar (8-28 bar) Bentone B45-2 RME...
32,63 35,25 8,50 28,28 31,65 34,66 37,45 9,00 29,95 33,59 36,71 39,65 9,50 35,37 38,74 41,85 10,00 37,23 40,78 44,06 The table applies to oil with a viscosity of 4,4 mm /s (cSt) with density 830 kg/m Bentone B45-2 RME...
Page 9
46,95 4903 9,00 42,40 44,95 47,39 49,71 51,92 9,50 44,75 47,45 50,02 52,47 54,80 10,00 47,11 49,94 52,66 55,23 59,69 The table applies to oil with a viscosity of 4,4 mm /s (cSt) with density 830 kg/m Bentone B45-2 RME...
Return pump Solenoid valve, 1 Pressure control pump Solenoid valve, 2 Inlet pump Measuring nipple, fan pressure Ignition electrodes Valve block Air intake Burner tube Brake plate Nozzle Burner l ange Pressure outlet pump Contactor for motor Bentone B45-2 RME...
Page 11
7-pole Euro plug (min. load feed) Ignition transformer Air damper Fan wheel Air intake Capacitor Damper motor Switch 0-I Motor Indicator, min. load Fan housing Switch I-II Indicator lamp, maximum load Inspection glass 4-pole Euro plug (max. load) Bentone B45-2 RME...
Bleed the oil system. The oil pump/oil preheater may be damaged if run dry. The vacuum should not fall below 0 bar in the suction line during start-up. 3.3.1 Proposed pipe routing for oil distribution systems without transport pump Oil i lter Bentone B45-2 RME...
Make sure the burner operations switch (S1) is off. Turn on the main switch. If any electrical connection is used other than that recommended by Bentone, there may be a danger of damage to property and personal injury. Bentone B45-2 RME...
You should then conduct a lue gas analysis and soot quantity measurement. Burner installation 3.7.1 Hole pattern Make sure the hole pattern on the boiler is designed for burner lange. Combustion device B45-2 Ø 135-(175) 200 M10-M12 Ø (195) 224-260 Bentone B45-2 RME...
Once the burner has been installed and commissioned, the seals of the various coupling elements should be checked (A). When a leak is detected, it is usually sufi cient to tighten the coupling element that is leaking. Recommended thread sealer. (Loctite 5188, 5400) Bentone B45-2 RME...
Once the burner has started and established a lame, it will be necessary to adjust the settings so that they are adapted to the installation in question and the fuel used at the time. Bentone B45-2 RME...
Set the desired position on the scale (C) using the set screw (D) (left turn reduces pressure loss, the brake plate is moved outward). If pulsation occurs, the changed pressure drop over the brake plate may result in the pulsation stopping Bentone B45-2 RME...
Once the red or orange cam has been moved, check whether the black cam must be changed. The black cam must be between the orange and red cam. Return the operations switch to Stage 1 and check combustion. Bentone B45-2 RME...
Page 20
Slide the white release button inwards and release. Changing the position of the motor until the gears engage with each other. Solenoid valve Stage 2 (black) Stage 2 (red) Stage 1 (orange) Closed damper (blue) Releasing buttonN.B. The upperposition is thestandard position Bentone B45-2 RME...
NB: When soiled, always replace nozzles with new nozzles. Do not clean. Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone B45-2 RME...
Press the burner together and lock using the nuts (H). Fit the Euro plugs and turn on the main current. Check combustion *. Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone B45-2 RME...
Set the damper motor notches as on the motor that has been replaced. Fit the Euro plugs and turn on the main current. Check combustion. * Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone B45-2 RME...
Use caution when operating the burner, surfaces may be hot. When servicing oil bearing components, check for oil leakage when the burner is commissioned after servicing. Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone B45-2 RME...
Oil temperature: 0 to+90°C Components Nozzle connection G 1/8” Vacuum manometer connection G 1/4” or G 1/8” Manometer connection G 1/8” Filter Suction line G 1/4” Metal plug G 1/4” Return plug Return line G 1/4” Pressure regulation Bentone B45-2 RME...
Page 27
Conversion to two-pipe system Remove the metal plug (7) G ¼”, i t the return plug (8) in the return line (9). Return plug are not included in products with one-pipe system, separately sold. 6.2.4 Solenoid valve Bentone B45-2 RME...
Page 29
The total resistance of these items is such that it can be the Q 46 l/h pump capacity at 0 bar applies. disregarded. In the tables no run longer than 100 m is listed, as experience shows this not to be required. Bentone B45-2 RME...
If burner operation is interrupted by the main switch or thermostat, a new start will take place once conditions as speciied in paragraph 1 are met. The machine blocks Red light in the machine is on. The burner is restarted by pressing the reset button. Bentone B45-2 RME...
45 μ A Max. output at dark, start: 5.5 μ A Enclosure type IP 40 Safety time 5 sec Check of photo current Photo current is measured using a DC ampmeter connected in series with the photocell. Bentone B45-2 RME...
If the reset button is instead kept pressed a second time for at least 3 seconds, you can, via an interface, obtain the corresponding information on a computer or lue gas analyser. To return to normal operation: Press the reset button for 1 second Bentone B45-2 RME...
8. FAULT LOCATION Burner will not start Symptom Causes Remedies Motor starts Unstable lame Burner pre-ventilates Excess air Adjust the damper Low oil pressure Check the oil pressure Flame formed Check the nozzle in relation to the combustion apparatus dimensions and the Burner trips Incorrect combustion apparatus settings ignition electrode position...
Page 37
OIL BURNERS MAINTENANCE INSTRUCTIONS General information If the burner starts but does not ignite Keep the boiler room clean. Ensure that the boiler Make an attempt to start the burner. room has permanent fresh air intake. Switch off before Never make close repeated start attempts. dismantling the oil burner.