Daikin ETVZ16S18EA6V Installer's Reference Manual page 99

Hide thumbs Also See for ETVZ16S18EA6V:
Table of Contents

Advertisement

EPRA14~18DAV3+W1 + ETVZ16S18+23EA6V+9W
Daikin Altherma 3 H HT F
4P644739-1 – 2021.02
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, always connect the backup heater
power supply and the earth cable.
The backup heater capacity can vary, depending on the indoor unit model. Make
sure that the power supply is in accordance with the backup heater capacity, as
listed in the table below.
Backup heater
Backup
type
capacity
*6V
*9W
(a)
6V
(b)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and ≤75 A per phase).
(c)
This equipment complies with EN/IEC 61000‑3‑11 (European/International Technical
Standard setting the limits for voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems for equipment with rated current ≤75 A) provided that the
system impedance Z
supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a system impedance Z
equal to Z
.
max
(d)
6T1
Connect the backup heater power supply as follows:
a
X6M
F1B
b
Q1DI
a Factory-mounted cable connected to the contactor of the backup heater, inside the
switch box (K5M)
b Field wiring (see table below)
Power supply
heater
2 kW
1N~ 230 V
4 kW
1N~ 230 V
6 kW
1N~ 230 V
2 kW
3~ 230 V
4 kW
3~ 230 V
6 kW
3~ 230 V
3 kW
3N~ 400 V
6 kW
3N~ 400 V
9 kW
3N~ 400 V
is less than or equal to Z
sys
max
9
Electrical installation
|
Maximum
running current
(a)
9 A
(a)
(b)(c)
17 A
(a)
(b)(c)
26 A
(d)
5 A
(d)
10 A
(d)
15 A
4 A
9 A
13 A
at the interface point between the user's
Installer reference guide
Z
max
0.22 Ω
0.22 Ω
less than or
sys
99

Advertisement

Table of Contents
loading

Table of Contents