Daikin ETVZ16S18EA6V Installer's Reference Manual page 160

Hide thumbs Also See for ETVZ16S18EA6V:
Table of Contents

Advertisement

10
|
Configuration
Installer reference guide
160
#
Code
N/A
[4-0D]
Number of zones
The system can supply leaving water to up to 2 water temperature zones. During
configuration, the number of water zones must be set.
#
Code
[4.4]
[7‑02]
[4.4]
[7‑02]
Description
Offset: ensures that the active desired room
temperature is always reached.
In heating mode, the space operation only
changes when the room temperature rises above
the desired heating temperature added by the
offset value.
Range: 1°C~10°C
Description
0: Single zone
Only one leaving water temperature zone:
a Main LWT zone
1: Dual zone
Two leaving water temperature zones. The
main leaving water temperature zone consists
of the higher load heat emitters and a mixing
station to achieve the desired leaving water
temperature. In heating:
a Additional LWT zone: Highest temperature
b Main LWT zone: Lowest temperature
c Mixing station
EPRA14~18DAV3+W1 + ETVZ16S18+23EA6V+9W
a
a
c
b
Daikin Altherma 3 H HT F
4P644739-1 – 2021.02

Advertisement

Table of Contents
loading

Table of Contents