Advertisement

Section 7
Logical node data model
The operational mode as given by the Mode control is shown in the data object Beh according to
priority rules described for Beh in clause 6 of IEC 61850-7-4.
The Beh shows the actual state of the function depending on the hierarchy described in clause 6 of
IEC 61850-7-4.
It is possible that the behavior is influenced also by other sources independent from the Mod, for
example Insertion of the test handle, IED configuration tool (PCM600), or LHMI.
In case the setting operation of a function is set to Off from the LHMI or PCM600, the Beh will be set
to Off independent of the value of the Mod.
The state Off can be set from the LHMI or the PCM600 for the functions having the setting operation.
The TEST and the TEST/BLOCKED mode can be operated locally from the LHMI or by using
PCM600.
Health
Health will reflect the current status of the IED HW and configuration. Possible values are: OK,
Warning, and Alarm.
Health indicates OK, Warning, or Alarm, depending on the IED status.
NamePlt
The name of the logical node and its relation to namespace definition are shown in the data object
NamePlt as specified for the SCL structure.
7.2

IEC 61850 data model description Edition 2

The IEC 61850 data model description Edition 2 is delivered in online help format on the IED
Connectivity package USB flash drive as part of the product delivery. The latest versions can be
downloaded from www.abb.com/protection-control.
7.2.1

Using the online help file

1.
Download the online help file from the link below and save the file to your local hard drive.
2.
Double-click the file.
3.
Clear the Always ask before opening this file check box.
4.
Click Open.
7.2.2

DO presence condition description

Table 3:
Condition
AtLeastOne
M
MFcond
Mmulti
Table continues on next page
32
(1MRK 511
444-WEN) for IEC 61850 data model description, Edition 2, SAM600–IO 2.2
Conditions used by the Logical Node description
Description
At least one of marked elements shall be present.
Element is mandatory.
Not yet defined.
At least one element shall be present; all instances have an instance number within range [1,
99] (see Part 7-1).
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 511 441-UEN Rev. C
GUID-B7C6120F-3A98-4DD4-8B4B-CCD2EEC9EE29 v3
GUID-0436EB93-842F-4908-85CB-93BCFED7AC93 v8
GUID-63E36A26-DCFF-49CD-9C58-CE783031532C v2
Switchgear control unit SAM600-IO
Communication protocol manual