Refrigerant R-410A Temperature/Pressure List (kPa/°C)
kPa
275
286
298
311
324
334
348
363
375
391
404
424
435
453
468
483
504
520
538
556
579
598
618
639
660
682
705
728
752
777

Operation Tools

The following tools will be used: 1) Liquid-level gauge; 2) Screwdriver; 3) Electric driven rotary hammer; 4)
Drill; 5) Flare Tool; 6) Torque wrench; 7) Open-end wrench; 8) Pipe cutter; 9) Leak detector; 10) Vacuum
pump; 11) Pressure gauge; 12) Multi-meter; 13) Hexagon wrench; 14) Measuring tape.
°C
kPa
-30
803
-29
823
-28
851
-27
879
-26
903
-25
937
-24
962
-23
994
-22
1020
-21
1050
-20
1090
-19
1110
-18
1150
-17
1180
-16
1220
-15
1250
-14
1280
-13
1320
-12
1350
-11
1400
-10
1440
-9
1470
-8
1520
-7
1560
-6
1600
-5
1640
-4
1680
-3
1730
-2
1780
-1
1820
CONNECT SERIES SERVICE MANUAL
°C
kPa
0
1880
1
1910
2
1960
3
2030
4
2080
5
2130
6
2180
7
2240
8
2290
9
2350
10
2410
11
2460
12
2510
13
2580
14
2650
15
2710
16
2770
17
2840
18
2910
19
2980
20
3050
21
3100
22
3180
23
3250
24
3320
25
3400
26
3480
27
3540
28
3630
29
3720
°C
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
101