7. Clearances to combustible materials using the HEATFLOW S5
The HEATFLOW S5 can only be used with single wall pipe, refer to the Annex section for
shielded single wall pipe.
The HEATFLOW S5 cannot be used with Heat shield (AC02762), a lowered ceiling, in an alcove
or in a mobile home.
The following below clearances for stoves using the HEAFLOW S5 must be respected, failure to do
so may result in damages to the stove, air ducts, blower and may also cause a fire.
THE HEATFLOW S5 CANNOT HAVE CLEARANCES TO COMBUSTIBLE MATERIALS REDUCED.
IT IS ABSOLUTELY ESSENTIAL TO POSITION THE STOVE IN ORDER TO REPECT THE REQUIRED
CLEARANCES FROM THE JACKET.
The following clearances for the stoves using the HEAFLOW S5 must be respected:
JACKET CLEARANCE WITH SINGLE WALL
PIPE CONNECTOR
CANADA
14 ½" (368mm)
A
12 ½" (318mm)
B
10" (254mm)
C
Installation Instruction HEATFLOW S5
WARNING
USA
14 ½" (368mm)
12 ½" (318mm)
10" (254mm)
English
DISTANCE FROM PIPE CONNECTOR
WITH SINGLE WALL PIPE CONNECTOR
CANADA
18" (457mm)
D
22 ¾" (578mm)
E
19 3/4" (502mm)
F
13
USA
18" (457mm)
22 ¾" (578mm)
19 3/4" (502mm)
46310A