Securing The Burner To The Boiler; Hinge Installation; Positioning The Probe - Electrode - Riello 554T40 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

5.6

Securing the burner to the boiler

Provide an adequate lifting system of the burner.
Boiler door must have a max. thickness of 90 mm,
refractory lining included. If the thickness is great-
er (max. 150 mm) a combustion head extension
WARNING
should be used, to be requested separately.
5.6.1

Hinge installation

Install the hinge 4), supplied as standard, as shown in Fig. 9.
S7392
5.7

Positioning the probe - electrode

Respect the positions shown in Fig. 11.
WARNING
Probe
D5104
4
~
40 mm
Installation
➤ Separate the combustion head assembly from the burner
body by removing nut 1) and removing the group A)(Fig. 10).
➤ Fix the group B)(Fig. 10) to the boiler plate 2), inserting the
supplied insulating gasket 3).
The seal between burner and boiler must be
airtight.
WARNING
A
Fig. 9
Electrode
Diffuser
2.0 - 3.0 mm
15
GB
1
Probe
Electrode
2,2
=
3
2
D6323
B
Fig. 10
Fig. 11
20064609