Flue
Deflector
300 min
Terminal
Assembly
Top View Rear Flue
Fig. 12
Plume
Displacement
Kit
Air Inlet
Fig. 13
7726858-01 (1/19)
*
Property Boundary Line
Opening
Window or Door
150mm
MIN.
Due to the nature of the boiler a plume of water vapour
will be discharged from the flue. This should be taken
into account when siting the flue terminal.
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance and
that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access, then a
suitable terminal guard must be provided.
*4. The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than 300mm in
accordance with the diagram opposite (Fig. 12).
Reduction to the boundary is possible down to 25mm
but the flue deflector kit or the appropriate Plume
Displacement Kit must be used. The nuisance
factor must still be taken into account when these
options are being considered.
If fitting a Plume Displacement Flue Kit, the air inlet
must be a minimum of 150mm from any opening
windows or doors (Fig. 13).
Before Installation
5
600 Heat
31