Technical Specifications; Technical Data - Baxi Heat 616 Installation And Service Manual

Gas fired wall mounted condensing boiler
Hide thumbs Also See for Heat 616:
Table of Contents

Advertisement

3

Technical Specifications

3
Technical Specifications
3.1

Technical Data

appliance Type
C
C
13
appliance Category
CAT I
Heat input Qn Hs (Gross)
Max
613 model
kW
14.88
616 model
kW
18.32
619 model
kW
21.75
625 model
kW
28.62
630 model
kW
34.35
Heat Output Pn
(Non Condensing 70° C Mean Water
Temp)
Max
613 model
kW
13
616 model
kW
16
619 model
kW
19
625 model
kW
25
630 model
kW
30
Max gas Rate (Natural Gas - G20)
(After 10 Mins)
m
/hr
3
613 model
1.42
616 model
1.75
619 model
2.07
625 model
2.73
630 model
3.27
Dynamic (nominal) inlet Pressure
(Natural Gas - G20)
mbar
20
with a CV of 37.78 MJ/m
3
Product Characteristics Database
(SEDBUK)
SaP 2009 annual Efficiency
613 model - 89.2%
616 model - 89.2%
619 model - 89.2%
This value is used in the UK Government's Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0063.
14
600 Heat
Horizontal
33
Flue Terminal
Dimensions
2H
Connections
Min
Gas Supply
Central Heating Flow
8.59
8.59
(use ONLY compression fitting)
Central Heating Return
8.59
(use ONLY compression fitting)
8.59
Condensate Drain
8.59
Outercase Dimensions
Overall Height
Casing Height
Min
Casing Width
7.5
Casing Depth
7.5
7.5
Clearances
7.5
Both Sides
7.5
Above Casing
Above Casing
Below Casing
Below Casing
Front (For Servicing)
Front (In Operation)
See Section 5.3.6 for full details !
Weights
Packaged Boiler Carton
Installation Lift Weight
Packaged Boiler Carton
Installation Lift Weight
CO/CO 2 Ratio
Flow Temperature (adjustable)
30° C to 80° C (± 5° C)
Recommended System
Temperature Drop
Condensing 20°C
625 model - 89.1%
630 model - 89.1%
Diameter
100mm
Projection
125mm
-
22mm
-
22mm
-
22mm
-
for 21.5mm
plastic waste pipe
-
790mm
Inc Flue Elbow
-
625mm
-
370mm
-
270mm
5mm Min
190mm Min
(Top Flue)
35mm Min
(Rear Flue)
35mm Min
(in Cupboard)
120 mm Min
500mm Min
5mm Min
19.4 kg (13-25)
17.4 kg (13-25)
21.5 kg (30)
19.5 kg (30)
Up to a maximum
of 0.004
300
250
200
150
100
50
0
0.0
0.2
nOx Class
6
Electrical Supply
230V~ 50Hz
(Appliance must be connected to an
earthed supply)
Power Consumption
Max Rate
613 model
W
17
616 model
W
20
619 model
W
23
625 model
W
33
630 model
W
44
External Fuse Rating
3A
internal Fuse Rating (Terminal Strip)
Fuse
1.6T
Electrical Protection
IPX4D
Water Content
litres
1.4 (13-25)
litres
1.7 (30)
Static Head
max
25 metres
Low Head
0.4m min
System Detail
fully pumped open vented & sealed systems
Pressure Switch
13/16/19 Model - Not Fitted
25/30 Model - Fitted
nOTE: All data in this section are nominal
values and subject to normal production
tolerances.
Pressure drop vs Flow
0.4
0.6
0.8
1.0
1.2
Flow (m
hr)
3
1.4
1.6
1.8
7726858-01 (1/19)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Heat 613Heat 619Heat 625Heat 630

Table of Contents