Section 6
Operating procedures
All the items that can be cleared are shown.
The content of the Clear menu depends on the configuration configured with PCM600.
2.
Select the item to be cleared with
3.
Press
4.
To clear other items, repeat the steps.
6.3

Changing the IED functionality

6.3.1

Defining the setting group

6.3.1.1

Activating a setting group

IED settings are planned in advance for different operation conditions by calculating setting
values to different setting groups. The active setting group can be changed manually from the
menu or by the PCM600 tool.
1.
Select Main menu/Settings/Active setting group/SETGRPS:1 and press
GUID-9BC3D595-CF08-42AF-B74E-0D3970A552DB V1 EN-US
Figure 36: Active setting group
2.
Select the setting group with
3.
Press
4.
Commit the settings.
42
, select OK to confirm the selection or Cancel to cancel the selection.
Do not switch off the auxiliary power supply to the IED before changes. For
example, when setting parameter changes are saved.
to confirm the selection or
Remember to document the changes you make.
or
.
IEC13000235-1-en.vsd
or
.
to cancel.
1MRK 500 125-UEN A
GUID-A9853F1B-78ED-4AEF-AAE2-C27FF3DAE408 v3
AMU0600439 v8
.