6.1.4

Through fault monitoring report

Through fault reports can be viewed via the user interface using either the PCM tool or the
local HMI. Additionally, the IED generates through fault reports those can be exported using
multiple ways.
6.1.4.1

Through fault monitoring tool

The through fault monitoring report can be viewed using a specific tool known as through
fault monitoring using PCM600 tool. This tool can store last 100 through faults and each
through fault details can be viewed using this tool. The collected data can either be retrieved
as a direct file transfer from the IED or be exported using PCM600 tool.
Starting the through fault monitoring tool
Proceed as follows to start the through fault monitoring tool from the IED level:
1.
Right click on the Plant Structure of an IED.
2.
Select the Through Fault Monitoring from the context menu as shown in
IEC18000083 V1 EN-US
Figure 24: Starting the through fault monitoring tool
The through fault reports are read from the IED and the tool gets started. By default,
Fault reports related to the latest function instances are displayed.
User interface
The through fault monitoring tool consists of Through Fault Monitoring tab. The tab contains
two sets of table; an overview of all individual through fault events and detailed report of a
selected through fault event, as shown in
Operation manual
IEC18000083-1-en.vsdx
Figure
25.
Section 6
Operating procedures