Lochinvar HWHC 44-370 G CE Installation, Commissioning, User & Maintenance Instructions page 98

Ecocharger hybrid gas fired condensing water heater with intergrated coil
Table of Contents

Advertisement

Code and description
F04 (lock out error)
Three unsuccessful
ignition attempts.
F05 (lock out error)
Too many flame errors
have been signaled.
F06 (blocking error)
Short circuit between
flame probe and earth
F07 (lock out error)
A flame has been detected
after the gas control valve
was closed.
F08 (lock out error)
Error message from safety
relay
F09 (lock out error)
Water temperature
protection.
98
Cause
No gas
Air in the gas pipes
Defect in the hot surface igniter circuit
Defect in the ionisation circuit
Supply voltage too low
Incorrect roof or wall flue terminal.
Recirculating flue gases.
Damaged cable in contact with metal
surface or bent flame probe.
Ceramic part of the flame probe is
broken/cracked.
Defective gas control valves
Flame detection before the gas control
valve opened.
Temperature at the top of the tank
exceeds 93 ºC.
Measure
Open the main gas supply valve and/or
the manual gas supply valve before the
gas control valve
Check supply pressure to the gas control
valve
If necessary, restore the gas supply
Bleed the air out of the gas pipe (see
section 7.9.2) and measure the supply
pressure and burner pressure.
Check that the hot surface igniter is
correctly connected (JP2).
Check the wiring of the hot surface
igniter.
Measure the resistance across the hot
surface igniter. This must lie between 2
and 10 Ohm (at room temperature).
Check that the hot surface igniter lights
up during ignition.
If necessary, replace the hot surface
igniter.
Check that the flame probe is correctly
connected (JP2)
Check the wiring of the flame probe
Measure the ionisation current. This must
be a minimum of 1.5 microA.
If necessary, replace the wiring.
Check the supply voltage, this must be 230
VAC(-15%, +10%)
Check that the correct roof or wall flue
terminal has been installed (see section
7.7).
If necessary, install the correct roof or
wall flue terminal.
Check that the roof or wall flue terminal
discharges into a permitted area.
Check the wiring and the flame probe.
Replace the wiring and/or flame probe if
necessary.
Check whether the ceramic part of the
flame probe is still intact, in the vicinity
of the air distribution plate of the burner.
If not the flame probe must be replaced.
Check whether there is still burner
pressure present, after the gas control
valves have closed.
Check whether a flame is still present,
after the gas control valves have closed.
If this is the case, the gas control valve
must be replaced.
Reset controller.
If the error appears again, replace the
controller.
Check that the circulation pump (if
present) is working
Check the position of temperature sensor
T
1
Reset controller