0311746_HWHC_44-63_II_ENEN_V2.6, 2022-10-17

Safety devices

Protection for the water heater

Water temperature protection
The controller (4) controls and monitors the safety of the water heater by means of
sensors T
and T
. S
is also used for protection of the water heater.
1
2
2
However, this is primarily intended for control of the solar heating system (see section
6.3.3).
The table explains the functioning of these temperature sensors.
Safety
Against frost:
- T
< 5 ºC
1
- T
< 5 ºC
2
Against overheating of
water:
- T
> 88 ºC
1
- T
> 88 ºC
2
- S
> 88 ºC
2
For extra safety
- T
> 93 ºC
1
- T
> 93 ºC
2
- S
> 93 ºC
2
Gas control valve
The controller opens the gas control valve so that gas can be supplied to the burner. As a
safety measure, the gas control valve has two valves. Both valves shut off the gas supply.
Fan
The fan (18) provides an optimum air supply when there is a heat demand. As a safety
feature, the fan ensures that any gases present in the combustion chamber are removed,
both before and after combustion. We refer to this as pre- and post-purge.
The fan speed is continuously monitored by the controller (4). The controller takes control
if the fan rpm varies too much from the value set.
Pressure switch
The pressure switch only guarantees the supply of air during pre-purging of the water
heater. If the pressure difference during pre-purging is sufficient, the pressure switch
closes. Refer to the general and electric specifications in the appendices (see section 12)
for the trip point for each water heater.
Note
The trip point of the pressure switch is not adjustable.
Description
The frost protection cuts in. The water is heated to
20 °C.
The high-limit safeguard serves to prevent
overheating and/or excessive formation of scale in
the appliance. If the high-limit safeguard is
activated, heating is stopped. This causes the
water in the tank to cool down. Once the water has
cooled sufficiently (T
< 81°C), the controller
1
resets the appliance.
A lockout error of the water heater controller takes
place. (see section 11) The controller must be
manually reset before the appliance can resume
operation. The reset may only be performed if T
81°C.
<
1
49