26
When the water heater starts, it will run through the following steps:
1.
The water temperature drops below the set temperature of (for example) 65°C. The
controller detects a heat demand and starts the operating cycle.
-
The icon
is activated.
-
The message HEAT DEMAND appears.
2.
Once demand is registered, the fan is started to vent any gases that may be present.
This phase is called pre-purge and lasts about 15 seconds.
-
The icon
is activated.
-
The message PRE PURGE appears.
3.
During the pre-purge, the pressure switch closes.
-
The icon
is activated.
-
The message PRESSURE SWITCH appears.
4.
This is then followed by the (pre-)glow of the hot surface igniter.
-
The icons
and
-
The icon
is activated.
5.
After a number of seconds pre-glow, the gas control valve is opened and ignition
takes place.
-
The icon
is activated.
-
The message IGNITION appears.
6.
After ignition, the flame is detected and the appliance will be running. This means
that actual heating has started:
-
The icon
is dimmed.
-
The icon
is activated.
-
The message RUNNING appears.
are dimmed
User part