Lochinvar HWHC 44-370 G CE Installation, Commissioning, User & Maintenance Instructions page 26

Ecocharger hybrid gas fired condensing water heater with intergrated coil
Table of Contents

Advertisement

26
When the water heater starts, it will run through the following steps:
1.
The water temperature drops below the set temperature of (for example) 65°C. The
controller detects a heat demand and starts the operating cycle.
-
The icon
is activated.
-
The message HEAT DEMAND appears.
2.
Once demand is registered, the fan is started to vent any gases that may be present.
This phase is called pre-purge and lasts about 15 seconds.
-
The icon
is activated.
-
The message PRE PURGE appears.
3.
During the pre-purge, the pressure switch closes.
-
The icon
is activated.
-
The message PRESSURE SWITCH appears.
4.
This is then followed by the (pre-)glow of the hot surface igniter.
-
The icons
and
-
The icon
is activated.
5.
After a number of seconds pre-glow, the gas control valve is opened and ignition
takes place.
-
The icon
is activated.
-
The message IGNITION appears.
6.
After ignition, the flame is detected and the appliance will be running. This means
that actual heating has started:
-
The icon
is dimmed.
-
The icon
is activated.
-
The message RUNNING appears.
are dimmed
User part