Expansion Valve; Other Components - Nibe F2040 Technical Manual

Air/water heat pump
Hide thumbs Also See for F2040:
Table of Contents

Advertisement

Expansion valve

The refrigerant is vaporised by reducing the ambient pressure.
The expansion valve controls the liquid refrigerant flow (480 pulses from completely open to completely closed).

Other components

Component
High pressure switch (BP1)
(63H1)
High pressure sensor (BP4)
Low pressure sensor (LPT)
Component
F2040-8:
Bottom drain pan heater (EB 11)
NIBE™ F2040
Needle
valve
Refrigerant
Pressure range
Breaking value: 41.5 bar
Max pressure: 45 bar
(4.5 MPa)
Reset value: 31.5 bar
1 – 46 bar (0.1 – 4.6 MPa)
Cut-out value 0.79 bar
Reset value: 1.75 bar
Ohm
529 Ω
Coil
Solenoid
Refrigerant
Working temp.
-30 – +85 °C
Surrounding area: -30 – +100
°C
Measurement medium: -30
– +120 °C
Output
100 W
Connection
Soldered connection
1/4'' flare connection with
Schrader valve.
1/4'' flare connection with
Schrader valve,
Voltage
230 V
Chapter 5 |
Component description
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

F2040-8F2040-16F2040-12