Ecoflam MAX 1 R Operating Instructions Manual page 14

Light oil burners
Hide thumbs Also See for MAX 1 R:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 6
EN
Start up
- Setting data table - Air regulation
NOZZLE
gph
spry
0.50
60°S
0.55
60°S
0.60
60°S
0.65
80°S
0.75
60°S
0.50
60°S
0.55
60°S
0.60
60°S
0.65
60°S
0.75
60°S
0.85
60°S
1.00
60°S
The settings above are basic settings.
These adjustment values are normally
suitable for commissioning the burner.
These values have been determined in
our test labs and are useful for the first
A
B
MAX 1
www.ecoflam-burners.com
PUMP
OUTPUT
bar
kg/h
12
1,75
12
1,84
12
1,92
12
2,4
12
2,8
12
1,75
12
1,84
12
1,92
12
2,4
12
2,8
12
3,1
12
3,8
switch-on as final setting must be done
using a combustion analyzer.
Favourable combustion values can be
achieved using the following nozzles:
A
MAX 1
B
FIRING HEAD SETTING
Pos.
2
2
Air damper setting (A).
MAX 4
To act on the screw in figure:
• to increase output, turn screwdriver
• to reduce output, turn screwdriver
Firing head setting (B).
To act on the screw in figure:
• turn Allen key till you reach the
MAX 4
AIR DAMPER SETTING
Pos.
4
4
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
clockwise
counterclockwise
requested value (index 0-4,5).
420010474601

Advertisement

Table of Contents
loading

This manual is also suitable for:

Max 4 rMax 1 low-nox tcMax 1 low-nox twMax 1 ln tc oMax 4 low-nox tcMax 4 low-nox tw ... Show all

Table of Contents