Welder / Generator Maintenance; Cleaning; Brush Removal And Replacement - Lincoln Electric Vantage 580 Operator's Manual

Hide thumbs Also See for Vantage 580:
Table of Contents

Advertisement

D-6
WeLDeR / GeNeRatOR
MaINteNaNCe
stORaGe: Store in clean, dry protected areas.
CLeaNING: Blow out the generator and controls peri-
odically with low pressure air. Do this at least once a
week in particularly dirty areas.
BRUsH ReMOVaL aND RePLaCeMeNt: It's nor-
mal for the brushes and slip rings to wear and darken
slightly. Inspect the brushes when a generator over-
haul is necessary.
CaUtION
• Do not attempt to polish slip rings while the
engine is running.
WaRNING
• service and Repair should only be performed by
Lincoln electric factory trained Personnel.
Unauthorized repairs performed on this equip-
ment may result in danger to the technician and
machine operator and will invalidate your factory
warranty. for your safety and to avoid electrical
shock, please observe all safety notes and pre-
cautions.
------------------------------------------------------------------------
MaINteNaNCe
GfCI MODULe testING aND ResettING
PROCeDURe
The GFCI module should be properly tested at least
once every month or whenever it is tripped. To properly
test and reset the GFCI module:
• If the module has tripped, first carefully remove any
load and check it for damage.
• If the equipment has been shut down, it must be
restarted.
• The equipment needs to be operating at high idle
speed and any necessary adjustments made on the
control panel so that the equipment is providing at
least 80 volts to the receptacle input terminals.
• The circuit breaker for this receptacle must not be
tripped. Reset if necessary.
• Push the "Reset" button located on the GFCI module.
This will assure normal GFCI operation.
• Plug a night-light (with an "ON/OFF" switch) or other
product (such as a lamp) into the Duplex receptacle
and turn the product "ON".
• Push the "Test" button located on the GFCI module.
The night-light or other product should go "OFF".
• Push the "Reset" button, again. The light or other
product should go "ON" again.
If the light or other product remains "ON" when the
"Test" button is pushed, the GFCI module is not work-
ing properly or has been incorrectly installed (miswired).
If your GFCI module is not working properly, contact a
qualified, certified electrician who can assess the situa-
tion, rewire the GFCI module if necessary or replace
the device.