208-240V Application without Neutral
CAUTION: The dryer must be grounded. A ground
lug has been provided for this purpose.
Input connection wiring must be sized properly to handle the
dryer's current draw. This information is printed on the dryer's
data label.
IMPORTANT: A strain relief must be used where the input
wiring enters the oven assembly.
Electrically Heated Models Only
The electrical input connections are made at the rear service
box located at the right upper section of the dryer. The ground
connection is made to a copper lug also provided in this area.
To gain access, remove rear service cover.
The only electrical input connections to the dryer are the
3-phase (3ø) power leads (L1, L2, L3, and sometimes neutral)
and ground. Single-phase (1ø) power for the control circuit
and for any single-phase (1ø) motors (if present) is done
internally to the dryer by the factory at the oven contactor.
No single-phase (1ø) input connection is required on a
3-phase (3ø) dryer.
The neutral will only be used on 4-wire service. This is typical
for 380-416V, 50 Hz.
CAUTION: The dryer must be grounded. A ground
lug has been provided for this purpose.
Input connection wiring must be sized properly to handle the
dryer's current draw. This information is printed on the dryer's
data label.
Electric Models Only
Single-Phase (1ø) Wiring Connections / Hookup
113280 - 3
3-Phase (3ø) Wiring Connections / Hookup

Gas Information ______________________

It is your responsibility to have all plumbing connections,
materials, and workmanship conform to local and state
regulations or codes of the country of destination. In the
absence of such codes, all plumbing connections, materials,
and workmanship must conform to the applicable local
requirements. In the USA this is the National Fuel Gas Code
ANSI Z223.1-LATEST EDITION, or in Canada, the Canadian
Installation Codes CAN/CGA-B149.1-M91 (Natural Gas) or
CAN/CGAB149.2-M91 (L.P. Gas) or LATEST EDITION.
In Australia, the fuel gas code is AS/NZS5601, local authority,
gas, electricity, and any other relevant statutory regulations.
It is important that gas pressure regulators meet applicable
pressure requirements, and that gas meters be rated for the
total amount of all the appliance Btu being supplied.
IMPORTANT: Failure to comply with these codes or
ordinances, and/or the requirements stipulated in this
manual, can result in personal injury and improper
operation of the dryer.
For ease of service, the individual gas supply line of each
dryer must have its own manual shutoff valve.
Failure to isolate or disconnect the dryer from supply as
noted can cause irreparable damage to the gas valve,
voiding the warranty.
The dryer and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa) for non-CE dryers or 50 mb for
CE dryers.
NOTE: The dryer must be isolated from the gas supply
piping system by closing its individual manual shutoff valve
during any pressure test of the gas supply system at test
pressures equal to or less than 1/2 psig (3.5 kPa) for non-
CE dryers or 50 mb for CE dryers.
Fire or explosion could result due to failure of
isolating or disconnecting the gas supply as noted.
NOTE: Undersized gas piping will result in ignition
problems, slow drying, increased use of energy, and can
create a safety hazard.