All commands are terminated with " <cr>" (carriage return)
All commands start with " Uuu", whereby " uu" stands for the address (00-31)
" *" can be used as a joker for any position in the address. The sensor always converts this in
its address. In case of more than one sensor, the joker must not be used, because otherwise
several slaves will answer
Commands that modify the instrument return the command with " OK". " EE-ERROR" replaces "
OK" if there was a problem changing the configuration
Report Level (and Temperature)
Parameter
Request:
Report Level (and Tem-
perature)
Response:
Report Level (and Tem-
perature)
PV in inches will be repeated if " Set number of floats" is set to 2. Hence 2 measured values can be
transmitted. PV value is transmitted as first measured value, SV as seconed measured value.
Information:
If the temperature should be transmitted in the Levelmaster protocol, then TV must be set in the
sensor to temperature.
PV, SV and TV can be adjusted via the sensor DTM.
Report Unit Number
Parameter
Request:
Report Unit Number
Response:
Report Level (and Temperature)
Assign Unit Number
Parameter
Request:
Assign Unit Number
Response:
Assign Unit Number
VEGAPULS 6X • Modbus and Levelmaster protocol
Length
4 characters ASCII
24 characters ASCII
The max. value for the PV to be transmitted is 999.99 inches (cor-
responds to approx. 25.4 m).
Length
5 characters ASCII
6 characters ASCII
Length
6 characters ASCII
6 characters ASCII
12 Supplement
Code/Data
Uuu?
UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1
level data not readable)
wwww = Warning number (0 no warn-
ing)
Code/Data
U**N?
UuuNnn
Code/Data
UuuNnn
UuuNOK
uu = new Address
103