Maintenance; Maintenance Of The Smoke System; Product Maintenance; Technical Data - Nobis B10 C ULISSE Instructions For Installation, Use And Maintenance Manual

Table of Contents

Advertisement

Use and Maintenance Manual model "B10 V ULISSE - B10 C ULISSE"
It is compulsory for the system to be grounded and
have a differential switch in compliance with cur-
rent laws. Also, ensure the socket is compatible with
the type of plug on the power cable used.
4

MAINTENANCE

Maintenance operations, excluding routine cleaning
(explained in the relevant paragraph), must be car-
ried out by authorized, technical staff. Remember,
before carrying out any maintenance operation, to
implement the following precautions:
• all parts of the product must be "cold";
• ensure there is no form of combustion whatsoever
(for example hot ash);
• use safety devices as per directive;
• remove the plug from the electrical socket;
• once maintenance has been carried out, reset
the product paying attention to re-activate all the
safety devices.

4.1 MAINTENANCE OF THE SMOKE SYSTEM

The chimney flue must always be kept clean,
since deposits of soot or fuel residue reduce the flow
rate, blocking the tube's draught, thus compromising
good operation of the product and, if in large quantities,
cause fire. it is mandatory to have the chimney cleaned
and checked by a qualified chimney sweep at least
once a year or after a prolonged stop for non-use of the
appliance. At the end of the check/maintenance, ask
for a report to be issued stating that the system is safe.
Failure to clean jeopardizes the safety of the system.

4.2 PRODUCT MAINTENANCE

Carry out maintenance at least once a year or on
each "Service Hours" signalling (signal appearing on
screen when the limit of working hours, over which
excellent operation is not guaranteed, have been
exceeded).
In this phase, the authorized technician should:
• completely and accurately clean the
smoke pipes;
• check the sealing status of all the gaskets;
• remove crushed pellet residue inside
the pellet tank;
• re-assemble all parts of the appliance;
• check correct operation and good quality of
combustion.
5

TECHNICAL DATA

This chapter gives the end user all information related
to the technical data of the product, its dimensions,
installation measurements, minimum distance to from
walls and furniture, sofas, etc. to be observed.

5.1 PRODUCT DATA SHEET

PRODUCT DATA SHEET
Brand
Model
Energy efficiency class
Direct thermal power (Kw)
Indirect thermal power (Kw)
Energy efficiency index
Useful efficiency (Nominal power %)
Useful efficiency (Reduced power %)
Warnings, installation procedures and periodic maintenance
must be observed as per pertaining instruction manual.

5.2 TECHNICAL FEATURES

Model
Weight of appliance (kg)
Ø air inlet (mm)
Ø smoke outlet pipe (mm)
Vol. max. heating* (m
)
3
Power introduced (kW)
Yield introduced (kW)
Yield (%)
CO 13% O
(%)
2
Tank capacity (kg)
Pellet hourly consumption (kg/h)
Autonomy (h)
Absorbed electrical power (W)
Electrical power supply (V-Hz)
Discharge gas flow (g/s)
Minimum draught (Pa)
Smoke temperature (°C)
* this value can vary depending on the type of energy
class of the house and the type of pellet used.
The outlined data are approximate and non-binding
and can vary depending on the type of pellet used.
The manufacturer reserves the right to make changes
for the purpose of improving product performance.
13
ENGLISH
EU 2015/1186
Nobis
B10 V ULISSE - B10 C ULISSE
A+
9.0
-
127.9
90.8
91.2
B10 V ULISSE - B10 C ULISSE
Reduced
Nominal
100
50
80
221
4.9
4.5
91.2
90.8
0.012
0.006
14
1,01
2,02
14
265
230-50
5.47
7.33
10
96
9.9
9.0
7
12
138

Advertisement

Table of Contents
loading

This manual is also suitable for:

B10 v ulisse

Table of Contents