Unigas C120A Installation Manual page 43

Lmv5x microprocessor controlled gas burners
Table of Contents

Advertisement

Flame detection probe
To clean/replace the detection photocell, proceed as follows:
1
Disconnect the system from the electrical power supply.
2
Shut off the fuel supply;
3
remove the photocell from its slot (see next figure);
4
clean the bulbe if dirty, taking care not to touch it with bare hands;
5
if necessary, replace the bulb;
replace the photocell into its slot.
Checking the detection current with electrode (natural gas)
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
Control box
Siemens LMV5x
Siemens LMV5
Minimum detection signal
6 µA (values on display:
50%)
Device
Flame
Detection electrode
Minimum detection signal (QRAx)
6 µA
43
PART IV: MAINTENANCE
Connector
X10-03.1
µA DC SCALE