Performance Curves - Unigas C120A Installation Manual

Lmv5x microprocessor controlled gas burners
Table of Contents

Advertisement

PART I: SPECIFICATIONS
How to read the burner "Performance curve"
To check if the burner is suitable for the boiler to which it must be instal-
lled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h / 860);
backpressure (data are available on the boiler ID plate or in the
user's manual).
Example:
Furnace input: 600kW
Backpressure: 4mbar
In the "Performance curve" diagram, draw a vertical line matching the
furnace input value and an horizontal line matching the backpressure
value. The burner is suitable if the intersection point A is inside the per-
formance curve.
Data are referred to standard conditions: atmospheric pressure at
1013mbar, ambient temperature at 15°C.

Performance Curves

C85A M-..
To get the input in kcal/h, multiply value in kW by 860.
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15° C
NOTE: The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests, but does not
represent the regulation range of the machine. On this diagram the maximum output point is usually reached by adjsuting the combustion head to its
"MAX" position (see paragraph "Adjusting the combustion head"); the minimum output point is reached setting the combustion head to its "MIN" position.
During the first ignition, the combustion head is set in order to find a compromise between the burner output and the generator specifications, that is why
the minimum output may be different from the Performance curve minimum
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
8
7
6
5
4
3
2
1
0
-1
100
200
C120A M-..
3
Stm
/h
C120A L-..
10
Campo di lavoro bruciatori
A
300
400
500
600
700
Power kW
Potenza kW
800
900
3
Stm
/h
3
Stm
/h

Advertisement

Table of Contents
loading

This manual is also suitable for:

C85a

Table of Contents