Appendix 3: UPS Firmware Upgrade
You can check the
interface of the RMCARD.
Method 1: Using Web Interface
1. Turn off the UPS via the [UPS->Master Switch].
2. Go to Firmware Version page via the [UPS->Information->Firmware Version].
3. Upload the UPS firmware by clicking Update then Choose File to select the location of
the UPS firmware file.
4. Click Submit to implement the update, and an upgrade success window will show up
after upgrade has completed.
5. Turn on the UPS via [UPS->Master Switch].
Method 2: Using FTP Command
FTP service needs to be Enabled before attempting to execute a Firmware Upgrade.
Use the following steps to upgrade the firmware via FTP:
1. Turn off the UPS.
2. Extract the update file to
3. Open a command prompt window
4. Login to the CyberPower Remote Management Card with FTP command, in the
command prompt type:
(1) ftp
(2) ftp > open
(3) To [current IP address of RMCARD] [port]; EX: To 192.168.22.126 21
(4) Input USER NAME and PASSWORD (same as the administrator account in web user
interface, see page 6 for default factory settings)
5. Upload the file, type:
ftp > bin
ftp > put XXX.bin
6. Upload is now complete, type:
ftp > quit
7. Turn on the UPS.
Note: 1. It may take about 5 mins to complete the update. Please do not carry out any
other actions or pull out the RMCARD during the UPS firmware update process.
Note: 2.The update progress can only display in web interface.
on the [UPS->Information] page on the web user
\