Error
Code
Excessive speed
E81
Positioning range error
E83
States of GS1 and GS2
E98
E99
States of GS1/GS2 and EDM
Other indication
Error
Code
Rotating
Blinking
NOTE:
Reset is not allowed in 10 second after trip.
NOTE:
When error E08, E11,E14 and E30 occur, reset operation by RS terminal or STOP/RESET
key is not accepted. In this case, reset by cycling power. If still same error occurs, perform
initialization.
Restoring Factory Default Settings
You can restore all inverter parameters to the original factory (default) settings according to
area of use. After initializing the inverter, use the powerup test in page 2-23 of the
Instruction manual to get the motor running again. If operation mode (std. or high
frequency) mode is changed, inverter must be initialized to activate new mode. To initialize
the inverter, follow the steps below.If you forget password that restrict setting (b031) and
(b037), you cannot cancel it. (So you cannot initialize when software lock is active, you
note that the setting password.
(1) Select initialization mode in b084.
(2) If b084=02,
(3) If b084=02,
(4) Set
01
in b180.
(5) The following display appears for a few seconds, and initialization is completed with
d001
displayed.
* Please change
b 0 3 7
(Function code display restriction), in case some parameters cannot be displayed.
Name
Name
Reset
Undervoltage
Waiting to restart
Restricted operation
command
Trip history initializing
No data
(Trip monitor)
Communication error
Auto-tuning
completed
Auto-tuning error
03
or 04, select initialization target data in b094.
03
or 04, select country code in b085.
from"0 4
(Basic display)" to
If the motor speed rises to "maximum frequency
(A004) x over-speed error detection level (P026)" or more,
the inverter will shut off its output and display the error
code.
If current position exceeds the position range
(P072-P073), the inverter will shut off its output and
display the error code.
States of GS1 and GS2 are inconsistent.
States of GS1/GS2 and EDM are inconsistent.
RS input is ON or STOP/RESET key is pressed.
If input voltage is under the allowed level, inverter shuts
off output and wait with this indication.
This indication is displayed after tripping before
restarting.
Commanded RUN direction is restricted in b035.
Trip history is being initialized.
No trip/waning data exists.
Communication between inverter and digital operator
fails.
Auto-tuning is completed properly.
Auto-tuning fails.
"0 0
(Full display)" in parameter
91
Cause(s)
Descriptions