Output Function Summary Table – This table shows all functions for the logical outputs
(terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions, related
parameters and settings, and example wiring diagrams are in "Using Intelligent Output Terminals"
on page 36.
Option
Terminal
Code
Symbol
00
RUN
01
FA1
FA2
02
03
OL
04
OD
05
AL
06
FA3
07
OTQ
UV
09
10
TRQ
RNT
11
ONT
12
13
THM
19
BRK
BER
20
Output Function Summary Table
Function Name
Run Signal
Frequency Arrival Type
1–Constant Speed
Frequency Arrival Type
2–Over frequency
Overload Advance
Notice Signal 1
Output Deviation
for PID Control
Alarm Signal
Frequency Arrival Type
3–Set frequency
Over/under Torque
Signal
Undervoltage
Torque Limited Signal
Run Time Expired
Power ON time Expired
Thermal Warning
Brake Release Signal
Brake Error Signal
ON
When the inverter is in Run Mode.
OFF
When the inverter is in Stop Mode.
ON
When output to motor is at the set frequency.
OFF
When output to motor is OFF, or in any
acceleration or deceleration ramp.
ON
When output to motor is at or above the set freq,
even if in accel (C042) or decel (C043) ramps.
OFF
When output to motor is OFF,
or at a level below the set frequency.
ON
When output current is more than the set
threshold (C041) for the overload signal.
OFF
When output current is less than the set threshold
for the overload signal.
ON
When PID error is more than the set threshold for
the deviation signal.
OFF
When PID error is less than the set threshold for
the deviation signal.
ON
When an alarm signal has occurred and has not
been cleared.
OFF
When no alarm has occurred since the last
cleaning of alarm(s).
ON
When output to motor is at the set frequency,
during accel (C042) and decel (C043).
OFF
When output to motor is OFF,
or is not at a level of the set frequency.
ON
Estimated motor torque exceeds
the specified level.
OFF
Estimated motor torque is lower than
the specified level.
ON
Inverter is in Undervoltage.
OFF
Inverter is not in Undervoltage.
ON
Torque limit function is executing.
OFF
Torque limit function is not executing.
ON
Total running time of the inverter exceeds
the specified value.
OFF
Total running time of the inverter does not exceed
the specified value.
ON
Total power ON time of the inverter exceeds
the specified value.
OFF
Total power ON time of the inverter does not
exceed the specified value.
ON
Accumulated thermal count exceeds
the C061 set value.
OFF
Accumulated thermal count does not exceed the
C061 set value.
ON
Output for brake release.
OFF
No action for brake.
ON
Brake error has occurred.
OFF
Brake performance is normal.
78
Description