TERMINALS
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
Terminal
Numbers
93, 94
24 V AC Power
Important: The common power connection (terminal 93) must be
connected to Earth. ABB Cylon recommend that this is done at
the 24 V AC transformer.
13 ... 15
Auxiliary Power: 18 V DC output on 2 terminals, 60 mA total
95, 96
RS-485 Port 1 (BACnet® MS/TP) screw terminal
MS/TP subnet terminator switch is located beside the port. If the switch is
towards the icon, then termination is
icon then termination is
39 ... 42
Sensor / RS-485 Port 2 (Cylon® room sensors or BACnet® MS/TP or Modbus
RTU)
The bus Terminator Switch is located beside the port. If the switch is
towards the icon, then termination is
icon then termination is
Universal Inputs
1 ... 12
When input is configured as Digital:
LED Off: open circuit or logic 'off'
LED On: logic 'on'
When input is configured as Resistor/thermistor:
LED Off: valid resistance connected (Note: 0 Ω is counted as
valid)
LED Slow blink: resistor/thermistor not connected
When input is configured as Analog:
LED intensity is modulated by the analog signal
When the LED is blinking:
Fast blink indicates error condition
Two short flashes followed by a value* indicates the input is in
an override state (overridden by
*Note: The LED intensity illustrates the value measured at the input
terminals. The flash indicates that this value has been overridden.
25 ... 38
UniPuts™ + Relay
When a Uniput channel is configured as an input, the LED signals are
identical to Universal Inputs above. When configured as an output the
following apply:
When output is configured as Digital:
• LED Off: open circuit or logic 'off'
• LED On: logic 'on'
When output is configured as Analog:
• LED intensity is modulated by the analog signal
When the LED is blinking:
• Fast blink indicates error condition
• Two short flashes followed by a value indicates the output is in an
override state (overridden by
Service Port (Micro USB)
Ethernet Ports
FBXi Operation
FBXi Series |
Description
and if the switch is towards the
in
.
out
and if the switch is towards the
in
.
out
).
HD
CXpro
or HOA).