WIRING
FBXi-X256, FBXi-X48
FBXi-8R8-X96, FBXi-8R8-H-X96
Ground
Common
CAUTION - DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED.
REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED BY THE MANUFACTURER.
DISPOSE OF USED BATTERIES ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS.
Supply Requirements
Supply Rating
FBXi-8R8(-H)-X96
FBXi-8R8(-H)-X96 + 1 x FLX
FBXi-8R8(-H)-X96 + 2 x FLX
FBXi-8R8(-H)-X96 + 3 x FLX
FBXi-X256/FBXi-X48
FBXi-X256/FBXi-X48 + 1 x FLX
FBXi-X256/FBXi-X48 + 2 x FLX
FBXi-X256/FBXi-X48 + 3 x FLX
FBXi-X256 + 4 x FLX
FBXi-X256 + 16 x FLX
FLX Power Connection
Auxiliary Power
BACnet Loading
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
24 V AC ±20 % 50/60 Hz
30 VA (no FLX modules)
42 VA
54 VA
66 VA
20 VA (no FLX modules)
32 VA
44 VA
56 VA
68 VA
|
|
68 VA
Proprietary FLX bus connector carries power and comms from
FBXi Series unit. FBXi can supply power to up to 3 FLX modules.
18 V DC / 60 mA output
¼ unit load device
FBXi Series |
Point Numbers
Terminal Numbers
FBXi Operation
Relay Common
(24 V only)
71