# LED
9
"Power"
10 "Low Bat"
11
"Radio Rec"
12 "UL Sens"
13 "ReOpen Sens"
14 "Center Loop"
15
"Open"
16
"Stop"
17 "Close"
18 "Magnetic Lock"
19 "Aux. Pwr"
20 "Siren"
E1
"AC VOLTAGE INPUT"
E2
"PROTECTION WORKING"
E3
"AC VOLTAGE OUTPUT"
VIKING TECHNICAL SUPPORT 1.800.908.0884
Status
Meaning
OFF
No power to control board or in Sleep Mode.
SOLID
Normal Condition.
FLASHING
Operator is running on batteries only. (pg 18-19)
OFF
Normal Condition.
SOLID
Batteries are low. Check power supply to the operator. (pg 18-19)
FLASHING
Batteries critically low. Check power supply to operator. (pg 18-19)
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the
Radio terminal. (pg 28-30)
OFF
Normal Condition.
Control Board is receiving an input from a device connected to the
SOLID
UL terminal or when more than one required Monitored 10K Sensor is
connected. (pg
OFF
Normal Condition.
Control Board is receiving an input from a device connected to the Re-
SOLID
Open terminal or when more than one required Monitored 10K Sensor is
connected.
(pg 6-7, 22, 28,
OFF
No voltage output on these terminals at the moment.
SOLID
An input from a device connected to the Center terminal. (pg
OFF
Normal Condition.
SOLID
An input from a device connected to the Open terminal. (pg
OFF
Normal Condition.
Control Board is receiving an input from a device connected to the Stop or
SOLID
has not learned the required monitored sensor(s). (pg
There is a problem with the required monitored sensor(s) connected to the
FLASHING
"UL" and/or "ReOpen input terminals. (pg
OFF
Normal Condition.
SOLID
An input from a device connected to the Close terminal. (pg 28)
At Closed Limit and Magnetic Lock Relay state is closed across "COM" &
OFF
"N.C.". (pg 34). Gate should be at the Close Limit.
Not at Closed Limit and Magnetic Lock Relay state is closed across "COM" &
SOLID
"N.O.". (pg 34). Gate should not be at the Close Limit.
OFF
No voltage output on these terminals at the moment.
SOLID
There is 24VDC output on these terminals at the moment.
OFF
Normal Condition.
SOLID
Second consecutive obstruction has been detected. (pg 24, 26)
FLASHING
Batteries are critically low.
SOLID
Normal Condition.
OFF
Incoming power to the optional EMI Board is not sufficient..(pg 19)
SOLID
Normal Condition.
EMI Board is damaged and circuit is not protected. Replace the optional EMI
OFF
Board.
SOLID
Normal Condition.
OFF
There is no output voltage from the optional EMI Board..(pg 19)
TROUBLESHOOTING
6-7, 22,
28)
32)
6-7,
28,
32)
28,
32)
6-7, 22,
28)
22)
Page 38
TS Ref#(s)
1, 6, 15
1-5
1-5
1-5
9, 10
9, 10, 14
9, 10, 14
9, 10
9, 10
9, 10
14
9, 10
1-5, 11-13
1-5
2
2-3
3 7