Unigas E140X Manual Of Installation - Use - Maintenance page 21

Lmv 2x/3x microprocessor controlled gas burners
Table of Contents

Advertisement

Mounting VD-R & PS-...
ActuatorVD-R
VD-R + PS
1. Gas pressure regulation is possible with VD-R and PS pressure sensor only.
WARNING! For US/CN installation, the output pressure must be monitoried by min. and max. pressure switches set
to +/- 20% of the setpoint.
2. Mounting on pipe. Sensor position: 5x DN according to MBE. Pipe fitting with female thread size ¼, mount sensor with
seal, observe torque.
3. The pressure sensor includes a vent limiter according to UL 353 and ANSI Z21.18/CSA 6.3. No venting required in loca-
tions where vent limiters are accepted by the jurisdiction.
4. Only PS pressure sensors specified by DUNGS are authorised to be connected to the VD-R's M12 interface.
5. Only PS cables specified by DUNGS are authorised to be used to connect the PS to the VD-R. Max. cable length 3 m.
Siemens VGD20.. e VGD40..
Siemens VGD20.. and VGD40.. gas valves - with SKP2.. (pressure governor)
- Connect the reference gas pipe (TP in figure; 8mm-external size pipe supplied loose), to the gas pressure nipples placed on the gas
pipe, downstream the gas valves: gas pressure must be measured at a distance that must be at least 5 times the pipe size.
- Leave the blowhole free (SA in figure). Should the spring fitted not permit satisfactory regulation, ask one of our service centres for a
suitable replacement.
Caution: the SKP2 diaphragm D must be vertical
WARNING: removing the four screws BS causes the device to be unserviceable!
ActuatorVD-V
M12 x 5 Pin
The actuator VD-V does not need any adjustment (funzione ON-OFF)
The actuator VD-R It must be combined with the PS sensor (include
regolatore di pressione)
21
PART II: INSTALLATION

Advertisement

Table of Contents
loading

This manual is also suitable for:

E115xE190x

Table of Contents