Technical Specifications - Siemens SIMATIC CP 4163-5 Operating Instructions Manual

Table of Contents

Advertisement

Technical specifications

6.1
Technical specifications
Note the information in the S7-4100 system manual /2/ (Page 41).
In addition to the information in the system description, the following technical specifications
apply to the module.
Table 6- 1
Technical specifications
Article number
Connection to PROFIBUS
Electrical data
Power supply
Current consumption
Active power loss
Insulation tested with
Permissible ambient conditions
Ambient temperature at -1000 ... 2000 m above sea level *
Relative humidity during operation
Maximum pollutant concentration
Operating altitude
Design, dimensions and weight
Module format
SIMATIC CP 4163-5
Operating Instructions, 12/2022, C79000-G8976-C589-01
Technical specifications of the CP 4163-5
Number
Design
Transmission speed
Via S7-4100 backplane bus
From backplane bus
Maximum current consumption on the
PROFIBUS interface when connecting
network components (for example, optical
network components)
During operation with the rack installed
horizontally
(CP vertically)
During storage
During transportation
6DL4163-5DX00-0XE0
1 x PROFIBUS interface
9-pin D-sub socket (RS485)
9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbps
1.5 / 3 / 6 / 12 Mbps
DC 15 V
233 mA
100 mA at 5 V
3.5 W
DC 707 V (Type Test)
-25 °C ... +70 °C
-40 °C ... +70 °C
-40 °C ... +70 °C
≤ 95% at 25 °C, no condensation
Acc. to ISA-S71.04 severity level G1, G2, G3
Up to 5000 m above sea level *
Compact module S7-4100, single width