Siemens SITRANS FUS1010 Quick Start Manual page 13

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS FUS1010:
Table of Contents

Advertisement

Quick Start Safety Information for Hazardous Areas
Note
Ratings under this heading apply to specific model families
Check Your Model Number:
FUS1010 7ME3533, FUH1010 7ME3603 only
FM-CSA installation
Read, understand and follow all safety instruction on the electronic media provided. This
equipment is rated for use in hazardous (classified) locations as stated below and must be
installed according to the 1010-443 installation drawing provided on the media. Failure to
install the equipment in the prescribed manner will result in unsafe operation. Follow all local
jurisdictional safety codes when operating this equipment. When properly installed the
equipment meets the following FM – CSA ratings:
Transmitter
● Explosionproof for Class I, Division1, Groups B, C, D;
● Dust-ignitionproof for Class II, Division 1, Groups E, F and G
● Intrinsically safe connections for Class I and II, Division 1, Groups A, B, C, D, E, F and G;
● Nonincendive for Class I, Division 2, Groups A, B, C and D;
● Suitable for Class II, Division 2, Groups B, E, F and G outdoor (Type 4X), Class III (CSA
Sensors
● Intrinsically safe Class I and II, Division 1, Groups A, B, C, D, E, F and G;
● Nonincendive for Class I, Division 2, Groups A, B, C and D;
● Suitable for Class II, Division 2, Groups B, E, F and G outdoor (Type 4X), Class III (CSA
● Temperature code T6 at an ambient of 40°C
ATEX installation
Read, understand and follow all safety instruction on the electronic media provided. This
equipment is rated for use in explosive atmospheres as stated below and must be installed
according to the 1010-464 installation drawing provided on the media. Failure to install the
equipment in the prescribed manner will result in unsafe operation. Follow all regional safety
laws when operating this equipment. When properly installed the equipment meets the
following ATEX ratings as stated in EC-Type Examination Certificate KEMA03ATEX1134
FUS1010 IP65 NEMA 4X & IP66 NEMA 7 Quick Start
Operating Instructions, 01/2013, A5E03086486-AC
only)
only)
Introduction
1.3 Safety Notes
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fuh1010Sitrans fue1010

Table of Contents