Service Level - Unigas E150X Manual Of Installation - Use - Maintenance

Gas burners microprocessor controlled lmv 2x/3x
Table of Contents

Advertisement

.
Press InFo to return to the display of phases.
Example: Error code 111 / diagnostic code 0
To reset, press InFo for a second. Record the codes and check the Error List to find the type of faults.

Service level

To enter the Service mode, press InFo until the display will show:
The service level shows all the information about flame intensity, actuators position, number and lock codes:
Parameter
Description
954
Flame intensity
121
% output, if set = automatic operation
922
Actuators position, 00=combustibile; 01= aria
161
Lock-outs number
701..725
Lock-outs History (see chapter 23 in the LMV2x manual)
1
.the first parameter will be "954": the percentage of flame is shown on the right. By pressinf + or - it is possible to scroll up/down the
parameter list.
2
Once the last parameter is accessed (143) by pressing + , the End message will blink.
3
PressPress InFo
for more than three seconds or for more than three seconds orto return to the normal display.
PART III: OPERATION