3.3

Mounting

Before mounting the inverter, you have to prepare expansion screws and a security screw.
Step 1. Install the mounting bracket
1. Use a level ruler to mark the position of the 3 holes on
the wall. Refer to Figure a. And drill 3 holes, 16mm in
diameter and 55mm in deep. Refer to Figure b.
2. Knock the expansion screw kit into the hole together
with a hammer. Refer to Figure c.
Note: Do not remove the nut unit in this step.
3. After tightening 2-3 buckles, the expansion bolts are
tight and not loose, and then unscrew the bolts, spring
washer, gasket. Refer to Figure c.
4. Install and fix the mounting bracket on the wall.
Refer to Figure d.
Step 2. Install the inverter on the mounting bracket. Then lock the inverter using the security
screw. Refer to Figure e and Figure f.
Set bracket horizontally.
Mark the holes position
a
on the wall.
C & D & E
M12
26N·m
d
DANGER
CAUTION
Ø 16mm; Depth: 55mm
b
Drill the holes.
e
Before filling the hole on the wall, ensure no damage on the electric wire and/or
water pipe inside the wall.
To prevent potential damages and injuries from inverter falling down, please hang
the inverter on the bracket, do not loosen grip unless confirm the inverter is well
mounted.
Expansion screw group
( M12; 3 suites)
c
f
10
3 Installation
3 Installation
E D C
B
A
A & B
M6 Security screw; 2.5N·m