Grounding - PrimeVOLT PV 4K6HB-60 User Manual

Single phase ess string inverter
Hide thumbs Also See for PV 4K6HB-60:
Table of Contents

Advertisement

4.1

Grounding

A protective earth (PE) terminal is equipped at the side of the inverter. Please be sure to connect this PE
terminal to the PE bar for reliable grounding. AWG 10 or 12 yellow green lines are recommended.
WARNING
CAUTION
Notes: Australia uses the TN-C-S earthing system which requires the neutral to be connected/bonded to the
earth to create a MEN (Multiple Earth Neutral) system:
L
PEN
Additional
Source Electrode
T
N-C
combined neutral
and protective
conductor (PEN)
Source Earth
in source of
supply, with PME
applied)
The inverter must be grounded; otherwise, there may be electric shock risk.
If the positive pole or negative pole of the PV array is required to be
grounded, then the inverter output (to AC grid) must be isolated by
transformer in accordance with IEC62109-1, -2 standards.
TN-C-S System
N
Link
PE
S
separate neutral (N)
and protective
conductors (PE)
within installation)
The bottom view
Installation
equipment
16
4 Electrical Connections
4 Electrical Connections
Grounding
Terminal