1600 W Flex Slot Platinum Hot-Plug Low Halogen Power Supply - Hitachi HA820 G2 User Manual

Table of Contents

Advertisement

CAUTION: This equipment is designed to permit the connection of the earthed
conductor of the DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode
This equipment must be located in the same immediate area (such as adjacent cabinets)
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between

1600 W Flex Slot Platinum Hot-plug Low Halogen Power Supply

Specification
Input requirements
Rated input voltage
Rated input frequency
Rated input current
Maximum rated input power
BTUs per hour
Power supply output
Rated steady-state power
Maximum peak power
The branch circuit overcurrent protection must be rated 27 A.
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC
supply system earthing electrode conductor is connected.
as any other equipment that has a connection between the earthed conductor of the same
DC supply circuit and the earthing conductor, and also the point of earthing of the DC
system. The DC system must be earthed elsewhere.
the DC source and the point of connection of the earthing electrode conductor.
200 VAC to 240 VAC 240 VDC for China only
50 Hz to 60 Hz
8.7 A at 200 VAC
7.5 A at 230 VAC
1734 W at 200 VAC 1727 W at 230 VAC
5918 at 200 VAC
5891 at 230 VAC
1600 W at 200 VAC to 240 VAC input 1600 W
at 240 VDC input
2200 W for 1 ms (turbo mode) at 200 VAC to
240 VAC input