Technical Specification
Model
AC-TA36-23
AC-TE36-20(48)(60)
AC-TA60-23
AC-TE60-20(48)(60)
AC-TA72-23
AC-TE72-20(48)(60)
AC-TW36-23
AC-TW60-23
AC-TW72-23
Model
Fan
Airflow
Speed
(CFM)
AC-TW36-23
max
1050
AC-TW60-23
max
1550
AC-TW72-23
max
2150
Supply water temperature: 176 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F
Model
Fan
Airflow
Speed
(CFM)
AC-TW36-23
max
1050
AC-TW60-23
max
1550
AC-TW72-23
max
2150
Supply water temperature: 140 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F
1. Recommended outlet air temperature for good comfort and optimized output.
2. Nominal output at given supply and return water temperature.
AC
Nozzle
Max Velocity
width x depth (in)
at nozzle (fpm)
38.4x2.6
2346
38.4x2.6
2346
58.5x2.6
2267
58.5x2.6
2267
77.8X2.6
2346
77.8X2.6
2346
38.4x2.6
2165
58.5x2.6
1791
77.8X2.6
2165
Output
Return water
Water flow
(MBH)
temp. (°F)
(GPM)
34.1
108
1.0
52.2
100
1.4
72.4
100
1.9
Water temperature: 176/140 °F
Room temperature: +64 °F
*1
Output
Return water
Water flow
(MBH)
temp. (°F)
(GPM)
34.8
118
3.1
49.8
108
3.2
73.7
113
5.5
Water temperature: 140/104 °F
Room temperature: +64 °F
*1
TE
72
Outlet Velocity
(fpm)
1974
1974
1860
1860
1974
1974
1785
1545
1785
Pressure
Output*
Outlet air
2
drop (kPa)
(MBH)
temp. (°F)
1.4
50.9
108
2.0
82.6
113
2.6
114.0
111
Pressure drop
Output*
Outlet air
2
(kPa)
(MBH)
temp. (°F)
10.9
28.0
90
8.7
46.4
91
17.2
64.5
91
60
Air Curtain
Select12 Series
Electric Heated
Nominal Length of unit
in inch
Voltage Code 600V
schwankgroup.com/schwankair
Outlet Velocity Uniformity
(%)
81
81
80
80
81
81
75
82
75
Water
Pressure
flow (GPM)
drop (kPa)
2.9
8.8
4.7
16.2
6.5
21.6
Water flow
Pressure drop
(GPM)
(kPa)
1.6
3.2
2.6
6.1
3.6
8.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents