Functional Test; Temperature Control - Schwank Select12 Series Manual

Table of Contents

Advertisement

Available languages

Available languages

Fan speed 1/2/3
Electric: Half/full power
Water: On/off (1 LED)
Fan speed 1/2/3
Remote control - on/off, fan speed and heating steps

Functional test

Functional test is started using the remote control.
Push and in
5 seconds
Fan and heatings steps are tested in 10-second
intervals which is indicated by lighted LEDs.
When the test is completed, all LEDs will flash for 30
seconds.
Heat step
On/off
Control panel - Unit with electrical heating or
water heating
On/off
Control panel - Unit without heating

Temperature control

If the temperature exceeds 122 °F, the fan runs at
full speed for 2 minutes to vent out the heat, if the
temperature rises above 122 °F again during the
following 5 minutes overheating alarm is deployed.
The red LEDs flash and all the buttons are locked.
1. Disconnect the power supply with the isolator
2. Determine the cause of overheating and rectify
3. Reconnect the unit.
switch.
the fault.
schwankgroup.com/schwankair